Installation space
<Installation space>
REQUIREMENT
When using the air conditioner under condition of
high humidity, attach the thermal insulator to the
side face and the rear side of the indoor unit.
Unit fixing bolt
• In case of wooden wall and wooden floor (AP0151 Model to AP0271 Model)
Use the four screw bolts (M8 × L50) for transportation and the two screw bolts attached to inside of the indoor unit.
• In case of wooden wall and wooden floor (AP0361 Model to AP0561 Model)
Use the two screw bolts (M8 × L50) for transportation and the four screw bolts attached to inside of the indoor unit.
• In case of models other than the above
Procure the six anchor bolts (M8 × L50 or longer) at the local site.
In case of fixing the indoor unit to the wall surface
Use the attached wall fixing bracket by inverting it at
upper side of the unit. Fix the indoor unit to the wall
surface using the attached screw bolts, anchor bolts
or etc. at two positions. A many holes for fixing the
indoor unit to wall surface and for fixing the indoor
unit itself are provided on the bracket. Sliding the
bracket right and left sides, select a position which
can securely fix the indoor unit and then fix it.
Screw bolts
Wooden wall
Anchor bolts
Concrete wall
Front side
(In case of right direction piping)
A hole on the wall fixing bracket for the indoor unit is
a long hole. Therefore the indoor unit can be fixed at
any position keeping clearance from 0 to 50mm.
As shown below, it is also possible to fix the indoor
unit without inverting the bracket. (In this case, keep
clearance with length of head of the bolt between the
indoor unit and the wall.)
0mm
50mm
77
200mm
500mm or more
or more
Front side
Clearance
(Height of head
of fixing bolt)