18. APPLIED CONTROL

18-1. Indoor Unit
18-1-1. Setup of Selecting Function in Indoor Unit
(Be sure to Execute Setup by a Wired Remote Controller)
<Procedure> Execute the setup operation while the unit stops.
5
6
1
1
CL
SET
Push
,
, and
The firstly displayed unit No. indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit is turned on.
2
Every pushing
UNIT
displayed. In this time, the fan of the selected indoor unit only is turned on.
3
Specify the item code (DN) using the setup temperature
4
Select the setup data using the timer time
(When selecting the DN code to "33", change the temperature indication of the unit from "°C"
to "°F" on the remote controller.)
5
Push
button. (OK if display goes on.)
SET
• To change the selected indoor unit, return to procedure
• To change the item to be set up, return to procedure
6
Pushing
button returns the status to normal stop status.
SET
CL
buttons simultaneously for 4 seconds or more.
button, the indoor unit numbers in the group control are successively