5. Indoor unit information data display (Displayed on the header unit only)
SW01
SW02
SW03
4
1 to 16
1 to 3
Receiving status of
indoor BUS communication
5
Indoor check code
6
Indoor horse power
7
Indoor request command
(S code)
8
Indoor PMV opening data
9
Indoor TA sensor data
10
Indoor TF sensor data
11
Indoor TCJ sensor data
12
Indoor TC1 sensor data
13
Indoor TC2 sensor data
NOTE) Indoor address No. is set up by exchanging SW02 and SW03.
SW03
SW02
Indoor address
1
1 to 16
SW02 setup number
2
1 to 16
SW02 setup number + 16
3
1 to 16
SW02 setup number + 32
6. Outdoor EEPROM write-in error code display (Displayed on the header unit only)
∗ The latest error code written in EEPROM of each outdoor unit is displayed.
(It is used when confirming the error code after power supply has been reset.)
Set SW01 to 03 as shown in the following table, and the push SW04 for 5 seconds or more to display an
error code.
SW01
SW02
SW03
1
1
16
The latest error code of the header unit 1 (U1)
2
The latest error code of the follower unit 1 (U2)
3
The latest error code of the follower unit 2 (U3)
4
The latest error code of the follower unit 3 (U4)
• 7-segment display A, B
Display A
D600
D601
Receiving time: [ ... ... 1], Not received: [ ... ... ... ]
B
B
No check code: [– – –]
0. 2, 0. 5, 0. 8, ... 1, 1. 2, 1. 7, ... 2, 2. 5, ... 3, 3. 2, ... 4, ... 5,
B
... 6, ... 8, 1 0, 1 6, 2 0
Data is displayed with hexadecimal [ ... ... 0 to ... ... F]
B
B
Data is displayed with hexadecimal
B
Data is displayed with hexadecimal
B
Data is displayed with hexadecimal
B
Data is displayed with hexadecimal
B
Data is displayed with hexadecimal
B
Data is displayed with hexadecimal
7-segment display A
[01] to [16]
[17] to [32]
[33] to [48]
Display contents
Display B
D602
D603
D604
Display contents
7-segment display
A
E. r
E. r
E. r
E. r
The latest error code of the header unit
The latest error code of the follower unit 1
The latest error code of the follower unit 2
The latest error code of the follower unit 3
144
B
1. – –
2. – –
3. – –