Toshiba MMU-AP0091H Installation Manual page 147

Super modular multi outdoor / indoor unit air conditioners
Hide thumbs Also See for MMU-AP0091H:
Table of Contents

Advertisement

14-2-2. Function to Sstart/Stop (ON/OFF) Indoor Unit from Outdoor Unit
The following functions of the indoor unit can start or stop by operation of the switches on the interface P .C. board of the header unit.
No.
Function
1
Cooling test
Changes the mode of all the connected indoor
operation
units collectively to cooling test operation.
Note) Control operation same as usual test
operation from remote control is performed.
2
Heating test
Changes the mode of all the connected indoor
operation
units collectively to heating test operation.
Note) Control operation same as usual test
operation from remote control is performed.
3
Batch start
Starts all the connected indoor units collectively.
Note) The contents follow to the setup of remote
controller.
Batch stop
Stops all the connected indoor units collectively.
4
Individual
Starts the specified indoor unit.
start
Notes)
• The contents follow to the setup of remote
controller.
• The other indoor units keep the status as they
are.
Individual stop
Stops the specified indoor unit.
Note) The other indoor units keep the status as
they are.
Individual test
Operates the specified indoor unit.
operation
Note) The other indoor units keep the status as
they are.
NOTE 1) This start/stop function only sends the signals from the outdoor unit to the indoor unit, such as start, stop,
operation mode, etc, but it does not resend the signals even if the indoor unit does not follow the sent signals.
NOTE 2) The above controls are not used during abnormal stop.
Outline
Interface P.C. board
7-segment display [A]
Setup/Release
[Setup]
Push SW04 for 2 seconds or more
with SW01"2", SW02"5", SW03"1".
[Release]
Return SW01, SW02, Sw03 to "1".
[Setup]
Push SW04 for 2 seconds or more
with SW01"2", SW02"6", SW03"1".
[Release]
Return SW01, SW02, Sw03 to "1".
[Setup]
Push SW04 for 2 seconds or more
with SW01"2", SW02"7", SW03"1".
[Release]
Return SW01, SW02, Sw03 to "1".
[Setup]
Push SW05 for 2 seconds or more
with SW01"2", SW02"7", SW03"1".
[Release]
Return SW01, SW02, Sw03 to "1".
[Setup]
Set SW01 "16" and set SW02 and
SW03 to address No. (1 to 64) to be
started, and then push SW04 for 2
seconds or more
[Release]
Return SW01, SW02, Sw03 to "1".
[Setup]
Set SW01 "16" and set SW02 and
SW03 to address No. (1 to 64) to be
stopped, and then push SW05 for 2
seconds or more
[Release]
Return SW01, SW02, Sw03 to "1".
[Setup]
Set SW01 "16" and set SW02 and
SW03 to address No. (1 to 64) to be
operated, and then push SW04 for
10 seconds or more
[Release]
Return SW01, SW02, Sw03 to "1".
7-segment display [B]
SW04
SW05
SW01 SW02 SW03
<Rotary switch>
147
7-segment display
Section A
Section B
[C
]
[ –C]
Section A
Section B
[H
]
[ –H]
Section A
Section B
[CH]
[ 11]
[ 11] is displayed on
Section B for 5 seconds.
Section A
Section B
[CH]
[ 00]
[ 00] is displayed on
Section B for 5 seconds.
Section A
Section B
[
]
[
]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 11] for 5 seconds
from operation-ON.
Section A
Section B
[
]
[
]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 00] for 5 seconds
from operation-OFF.
Section A
Section B
[
]
[
]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ FF] for 5 seconds
from test operation-ON.