5-7. Branching Kit Connection Method
[1] Branch joint
<Gas side>
Pipe in use
Socket
Outlet (2)
on the site
Inlet
Outlet (1)
To outdoor unit
Gas side branch joint
<Liquid side>
Outlet (1)
Pipe in use
on the site
Inlet
Socket
To outdoor unit
• Installation direction of branch pipe
Install the branching pipes so that it branch either
vertically or horizontally.
Both directions
are possible.
In case of vertical
installation
<Gas/Liquid side>
A
(Horizontal line)
(A view)
(Horizontal line)
(B view)
<In case of horizontal installation>
NOTE :
• Install the branch pipes horizontally or vertically so
that they are branched evenly.
• Install the branching joint within ±15 degrees.
Pipe in use on the site
Socket
To other branching
pipe or indoor unit
Socket
Socket
To other branch-
ing pipe or indoor
unit
Pipe in use
on the site
Socket
Outlet (2)
Gas/Liquid side branch joint
B
Within
± 15 degrees
Within
± 15 degrees
NOTE :
Install the branch pipes horizontally or vertically so
that they branch evenly.
Install the branching joint within ± 15 degrees.
Heat insulating for pipes
(Branching Joint)
• In order to prevent dripping at the place where the
insulation provided with the branching kit meets the
insulating material obtained on the site, butt the two
types of insulation up against each other, and then
wrap the seam between the two types of insulation
in at least 10mm of the insulating material (in use
on the site).
<Gas/Liquid side>
Butt together
Heat insulator
Heat insulator
for piping
in package
(in use on the site)
150
Branching joint
Heat insulator (in use on the site)
by 10mm or more thickness.
• On the gas-side pipe, use insulation that can
withstand heat of 120°C or higher. For the branch
pipe, either use a commercially available coupling
cover (for T-shape) that is at least 10mm thick, or
else insulate the pipe as shown in the figure at
below.
• After applying insulation as outlined above, tape the
insulation in place.
Taping (in use on the site)
Heat insulator
(in use on the site)
20
Butt together
Heat insulator for piping
(in use on the site)
Butt together
Heat insulator
(in use on the site)

Hide quick links: