Toshiba MMU-AP0091H Installation Manual page 127

Super modular multi outdoor / indoor unit air conditioners
Hide thumbs Also See for MMU-AP0091H:
Table of Contents

Advertisement

12-1. Address re-setup for central control of the
super-digital inverter and the digital inverter
POINT 1
When controlling collectively the super-digital inverter and the digital inverter, the adaptor named "1 : 1 model"
connection interface (TCB-PCNT30TLE) is necessary.
1. Cabling connection of control wiring
Attach an adaptor per 1 group control operation (including individual control).
Connect the adaptor to the header indoor unit in the group control. (For details, see POINT 3 .)
Central
control
devices
U3
U4
Adaptor
2. Cabling connection diagram with indoor control P.C. board
• For details, refer to Installation Manual.
• Parts included in the single-point chain line are optional accessories.
• There is non-polarity on the cables connected to U3 and U4 terminals.
Central control wiring
Indoor unit
Indoor unit
Indoor
Indoor
control
control
P.C. board
P.C. board
A
B
A
B
Remote
controller
Connecting
terminal block
U3 U4
for control wiring
BLU
BLU
1
2
1
2
CN40 (BlU)
CN51 (RED)
"1:1 model"
connection interface
Indoor unit
U3
Indoor
control
Adaptor
P.C. board
A
B
WHI
1
1
1
1
RED
2
2
2
2
RED
3
3
3
3
RED
4
4
4
4
RED
5
5
5
5
127
Indoor unit
Indoor unit
U4
Indoor
Indoor
control
control
P.C. board
P.C. board
A
B
A
Remote
controller
CN50 (WHI)
Indoor control
P.C. board
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents