Solar/Group "4 - Viessmann Vitodens 200-W Installation Instructions Manual

45 and 60 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

DHW/group "3"
Coding in the delivered condition
71:0
DHW circulation pump:
"ON" according to time
program (only for weath-
er-compensated control
units)
72:0
DHW circulation pump:
"ON" according to time
program (only for weath-
er-compensated control
units)
73:0
DHW circulation pump:
"ON" according to time
program (only for weath-
er-compensated control
units)

Solar/group "4"

Select "Solar" for weather-compensa-
ted control unit (see page 79).
Select "4" for constant temperature con-
trol unit (see page 79).
Coding
Coding in the delivered condition
00:8
Start temperature differ-
ential for solar circuit
pump 8 K
01:4
Stop temperature differ-
ential for solar circuit
pump 4 K
02:0
Solar circuit pump not
speed-controlled
(cont.)
Possible change
71:1
"OFF" during DHW heating
to set value 1
71:2
"ON" during DHW heating
to set value 1
72:1
"OFF" during DHW heating
to set value 2
72:2
"ON" during DHW heating
to set value 2
73:1
"ON" from once per hour
to
for 5 min up to 6 times per
73:6
hour for 5 min during the
time program
73:7
Constantly "ON"
Note
The solar group is only displayed if a
solar control module, type SM1, is con-
nected.
Possible change
00:2
Start temperature differen-
to
tial adjustable from 2 to
00:30
30 K
01:1
Stop temperature differen-
to
tial adjustable from 1 to
01:29
29 K
02:1
Variable speed solar circuit
pump with wave packet
control
02:2
Solar circuit pump speed-
controlled with PWM con-
trol
Code 2
93