Heating Circuit 1, Heating Circuit 2, Heating Circuit 3/Group "5 - Viessmann Vitodens 200-W Installation Instructions Manual

45 and 60 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Code 1

Heating circuit 1, heating circuit 2, heating circuit 3/group "5"

Select "Heating circuit ..." for weather-
compensated control unit (see
page 65).
Coding
Coding in the delivered condition
Priority DHW heating
A2:2
Cylinder priority applica-
ble to heating circuit
pump and mixer
Economy function, outside temperature
A5:5
With heating circuit pump
logic function (economy
control): heating circuit
pump "OFF" when the
outside temperature (OT)
is 1 K higher than the set
room temperature (RT
OT > RT
weather-compensated
control units)
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
72
)
set
+ 1 K (only for
set
With heating circuit pump logic function: heating cir-
cuit pump "OFF"
OT > RT
+ 5 K
set
OT > RT
+ 4 K
set
OT > RT
+ 3 K
set
OT > RT
+ 2 K
set
OT > RT
+ 1 K
set
OT > RT
set
OT > RT
- 1 K
set
OT > RT
- 9 K
set
Select "5" for constant temperature con-
trol unit (see page 65).
Possible change
A2:0
Without cylinder priority ap-
plicable to heating circuit
pump and mixer
A2:1
Cylinder priority only appli-
cable to mixer
A2:3
Reduced priority for mixer:
to
the heating circuit receives
A2:15
a reduced amount of heat.
A5:0
Without heating circuit
pump logic function
A5:1
With heating circuit pump
to
logic function: heating cir-
A5:15
cuit pump "OFF"; see fol-
lowing table