Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
dC
dd
dE
dF
E0
126
Weath.-
System char-
comp.
acteristics
X
Control mode
without room
influence
X
Control mode
without room
influence
X
Control mode
without room
influence
X
Control mode
without room
influence
X
Control mode
Cause
Measures
Short circuit,
Check room tem-
room temper-
perature sensor,
ature sensor,
heating circuit 3
heating circuit
3 (with mixer)
Lead break,
Check room tem-
room temper-
perature sensor,
ature sensor,
heating circuit 1
heating circuit
and remote control
1 (without
settings (see
mixer)
page 160)
Lead break,
Check room tem-
room temper-
perature sensor,
ature sensor,
heating circuit 2
heating circuit
and remote control
2 (with mixer)
settings (see
page 160)
Lead break,
Check room tem-
room temper-
perature sensor,
ature sensor,
heating circuit 3
heating circuit
and remote control
3 (with mixer)
settings (see
page 160)
Fault, exter-
Check connections
nal LON sub-
and LON subscrib-
scriber
ers