Viessmann Vitodens 200-W Installation Instructions Manual page 103

45 and 60 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
d7:0
Heating circuit pump
stays in control mode at
signal "External de-
mand"
d8:0
No operating program
changeover via EA1 ex-
tension
E1:1
Never adjust
E2:50
With remote control: No
display correction for the
actual room temperature
(only for weather-com-
pensated control units)
E5:0
Never adjust
F1:0
Screed drying disabled
(only for weather-com-
pensated control units)
F2:8
Time limit for party mode
or external operating pro-
gram changeover via key:
8 h (only for weather-
compensated control
units)
*1
In the "Heating and DHW" program, party mode ends automatically when the
system changes over to operation with standard room temperature.
*1
(cont.)
Possible change
d7:1
Heating circuit pump stops
at signal "External de-
mand" (subject to coding
addresses 3A, 3b and 3C)
d7:2
Heating circuit pump stops
at signal "External de-
mand" (subject to coding
addresses 3A, 3b and 3C)
d8:1
Operating program
changeover via input DE1
at EA1 extension
d8:2
Operating program
changeover via input DE2
at EA1 extension
d8:3
Operating program
changeover via input DE3
at EA1 extension
E2:0
Display correction –5 K
to
to
E2:49
Display correction –0.1 K
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
F1:1
Screed drying adjustable in
to
accordance with 6 selecta-
F1:6
ble temperature/time pro-
files (see page 154)
F1:15
Constant flow temperature
20 °C
F2:0
No time limit for party
mode
F2:1
Time limit adjustable from 1
to
to 12 h
F2:12
Code 2
*1
*1
103