Commissioning, inspection, maintenance
Further details regarding the individual steps
Connecting the control unit to the LON
The LON communication module must
be plugged in (if installed as an acces-
sory, see the LON communication mod-
ule installation instructions).
Note
The data transfer via LON can take sev-
eral minutes.
Example: Single boiler system with
Vitotronic 200-H and Vitocom 200
Set the LON subscriber numbers and
further functions via code 2 (see the fol-
lowing table).
All coding addresses in the table are listed in the "General" group.
Boiler control unit
LON
Subscriber no. 1.
Code "77:1"
Control unit is fault
manager.
Code "79:1"
Control unit transmits
the time.
Code "7b:1"
Control unit transmits
outside temperature.
Set code "97:2".
60
Vitotronic 200-H
LON
Subscriber no. 10.
Code "77:10"
Control unit is not
fault manager.
Code "79:0"
Control unit receives
the time.
Set code "81:3".
Control unit receives
outside tempera-
ture.
Set code "97:1".
(cont.)
Note
In the same LON system, the same sub-
scriber number must not be allocated
twice.
Only one Vitotronic may be program-
med as fault manager.
Vitotronic 200-H
LON
Subscriber no. 11.
Set code "77:11".
Control unit is not
fault manager.
Code "79:0"
Control unit receives
the time.
Set code "81:3".
Control unit receives
outside tempera-
ture.
Set code "97:1".
Vitocom