Boiler/Group "2; Dhw/Group "3 - Viessmann Vitodens 200-W Installation Instructions Manual

45 and 60 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Boiler/group "2"

Select "Boiler" for weather-compensa-
ted control units (see page 65).
Coding
Coding in the delivered condition
Single/multi-boiler system
01:1
Single boiler system (only
for constant temperature
control units)
Boiler number
07:1
Boiler number in multi
boiler systems (only for
constant temperature
control units)
Burner service in 100 hours
21:0
No set service interval
(hours run)
Service interval in months
23:0
No burner service inter-
val
Service status
24:0
No "Service" indication
on the display
Filling/Venting
2F:0
Venting program/fill pro-
gram disabled

DHW/group "3"

Select "DHW" for weather-compensa-
ted control unit (see page 65).
Select "2" for constant temperature con-
trol unit (see page 65).
Possible change
01:2
Multi boiler system with
Vitotronic 300-K
07:2
Boiler number 2 to 4 in mul-
to
ti boiler systems
07:4
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10,000 h
One step ≙ 100 h
23:1
Interval adjustable from 1
to
to 24 months
23:24
24:1
"Service" shown in the
display. The address is set
automatically and must be
reset manually after a serv-
ice.
2F:1
Venting program enabled
2F:2
Fill program enabled
Select "3" for constant temperature con-
trol unit (see page 65).
Code 1
69