Viessmann Vitodens 200-W Installation Instructions Manual page 128

45 and 60 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
E7
X
E8
X
128
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
Cause
Measures
Ionisation
Check ionisation
current too
electrode:
low during
■ Distance to burn-
calibration
er gauze assem-
bly (see page 46)
■ Electrode con-
tamination
■ Connecting lead
and plug-in con-
nections
Check flue system;
remedy flue gas re-
circulation if re-
quired.
Press reset button
R.
The ionisa-
Check gas supply
tion current
(gas pressure and
lies outside
gas flow switch),
the permissi-
gas train and con-
ble range
necting lead.
Check allocation of
gas type (see
page 36).
Check ionisation
electrode:
■ Distance to burn-
er gauze assem-
bly (see page 46)
■ Electrode con-
tamination
Press reset button
R.