Code 2
Solar/group "4"
Coding in the delivered condition
03:10
Temperature differential
for the start of speed con-
trol 10 K
04:4
Controller amplification of
the speed control 4 %/K
05:10
Minimum solar circuit
pump speed 10 % of
maximum speed
06:75
Maximum speed of the
solar circuit pump 75 % of
the maximum possible
speed
07:0
Solar circuit pump inter-
val function OFF
08:60
Set DHW temperature
(maximum cylinder tem-
perature) 60 °C
09:130
Maximum collector tem-
perature (to protect sys-
tem components) 130 °C
0A:5
Temperature differential
for stagnation time reduc-
tion 5 K
Reduction in the speed of
the solar circuit pump to
protect system compo-
nents and heat transfer
medium.
0b:0
Frost protection function
for solar circuit OFF
0C:1
Delta-T monitoring ON
94
(cont.)
Possible change
03:5
Temperature differential
to
adjustable from 5 to 20 K
03:20
04:1
Controller amplification ad-
to
justable from 1 to 10 %/K
04:10
05:2
Min. speed of the solar cir-
to
cuit pump is adjustable
05:100
from 2 to 100 %
06:1
Maximum speed of the so-
to
lar circuit pump is adjusta-
06:100
ble from 1 to 100 %
07:1
Solar circuit pump interval
function ON
The solar circuit pump
starts for short cycles to
capture the collector tem-
perature more accurately.
08:10
Set DHW temperature ad-
to
justable from 10 to 90 °C
08:90
09:20
Temperature adjustable
to
from 20 to 200 °C
09:200
0A:0
Stagnation time reduction
is disabled
0A:1
Temperature differential
to
adjustable from 1 to 40 K
0A:40
0b:1
Frost protection function
for solar circuit switched on
(not required with
Viessmann heat transfer
medium).
0C:0
Delta-T monitoring OFF