Fault codes
(cont.)
Dis-
Const.
played
fault
code
E1
X
E2
X
E3
X
E4
X
E5
X
E6
X
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner blocked Fault, 24 V
X
Burner blocked Fault, flame
X
Burner blocked System pres-
Troubleshooting
Cause
Measures
Ionisation
Check gap be-
current too
tween ionisation
high during
electrode and
calibration
burner gauze as-
sembly (see
page 46).
In open flue opera-
tion, prevent high
incidence of dust in
the combustion
air.
Press reset button
R.
Heating water
Ensure adequate
flow rate too
circulation volume.
low during
Check flow switch.
calibration.
Flow switch
Remove scaling
has shut
and blockages.
down.
Press reset button
R.
Heat transfer
Ensure adequate
too low during
heat transfer.
calibration.
Press reset button
Temperature
R.
limiter has
shut down.
Replace control
supply volt-
unit.
age
Replace control
amplifier
unit.
Top up with water.
sure too low
127