Heating Circuit 1, Heating Circuit 2, Heating Circuit 3/Group "5 - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Solar/group "4"
(cont.)
Coding
Coding in the delivered condition
Speed control solar circuit pump
02:0
Solar circuit pump is not speed-
controlled.
Cylinder maximum temperature
08:60
Set DHW temperature (maximum
cylinder temperature) 60 °C.
Stagnation time reduction
0A:5
Temperature differential for stagna-
tion time reduction (reduction in
the speed of the solar circuit pump
to protect system components and
heat transfer medium) 5 K.
Flow rate solar circuit
0F:70
Solar circuit flow rate at the maxi-
mum pump speed 7 l/min.
Extended solar control functions
20:0
No extended control function ena-
bled.

Heating circuit 1, heating circuit 2, heating circuit 3/group "5"

Select "Heating circuit ..." for weather-compensated
control unit (see page 51).
Possible change
02:1
Solar circuit pump is speed-control-
led with wave packet control.
02:2
Solar circuit pump is speed-control-
led with PWM control.
08:10
Set DHW temperature adjustable
to
from 10 to 90 °C.
08:90
0A:0
Stagnation time reduction disabled.
0A:1
Temperature differential adjustable
to
from 1 to 40 K.
0A:40
0F:1
Flow rate adjustable from 0.1 to
to
25.5 l/min;
0F:255
1 step
20:1
Additional function for DHW heating.
20:2
Differential temperature control 2.
20:3
Differential temperature control 2
and ausiliary function.
20:4
Differential temperature control 2 for
central heating backup.
20:5
Thermostat function.
20:6
Thermostat function and auxiliary
function.
20:7
Solar heating via external heat ex-
changer without additional tempera-
ture sensor.
20:8
Solar heating via external heat ex-
changer with additional temperature
sensor.
20:9
Solar heating of two DHW cylinders.
Select "5" for constant temperature control unit (see
page 51).
Code 1
0.1 l/min.
55