Programming For Access Control - ADEMCO Vista-128B PLUS Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Table of Contents

Advertisement

Programming for Access Control

VistaKey
See the VistaKey-SK Installation and Setup Guide for
the detailed programming instructions.
VistaKey Dialer Enables
When the VistaKey is installed with an alarm system,
the system defaults are set so that the system does not
send reports to the central station. The programming is
accomplished in field 1∗35 for the following events:
ACS Troubles - To enable or disable ACS trouble
reporting.
ACS Bypasses - To enable or disable ACS bypass
reporting.
ACS System - To enable or disable ACS system
reporting, (i.e., ACS module reset).
ACS Alarms - To enable or disable ACS alarm
reporting.
Dialer (Trace) - To enable or disable access
grant/denial events sent to the central station.
The PassPoint ACS can dedicate some of its inputs for
use as regular VISTA-128B PLUS hardwired zones (the
zone response type is ACS). The PassPoint ACS can
also utilize the VISTA-128B PLUS dialer for reports to
the central station.
Using ACS Zone Inputs
If the PassPoint ACS has uncommitted zones, these
may be used by the VISTA-128B PLUS as hardwired
zones. To program for ACS zone inputs, perform the
following steps:
Step
Action
Enter Zone Programming in the #93 Menu
1
Mode.
2
Program this zone as any other zone. Indicate
the input type as ACS (10).
3
Enter the PassPoint ACS's zone ID (00-31)
See Zone Programming in the Programming Guide for a
detailed explanation.
PassPoint Dialer Events
All PassPoint ACS events can be sent to the VISTA-
128B PLUS dialer via the VGM. These events will also
be logged into the control's event log. This is enabled in
the PassPoint ACS. See the PassPoint ACS
documentation for a detailed explanation.
Programming the VISTA Gateway Module
See the PassPoint ACS instructions to program the
VISTA Gateway Module.
Access Control of an Entry/Exit Point Using
VistaKey or PassPoint
The control can send entry and exit requests to the
VistaKey or PassPoint ACS utilizing keypads and
button-type (BR) RF transmitters. A zone is
programmed with a response type 27 (Access Point) and
an appropriate input type (console, RF).
Using the Alpha Keypad
Step
Action
1
Enter Zone Programming in the #93 Menu
Mode.
2
Program the zone with a response type 27
(Access Point).
3
Enter the access point number (00-31) of the
door.
4
Program whether this is an entry or exit point.
5
Enter the partition number.
6
Enter the input type as CS (09).
7
Enter the keypad ECP address.
See Zone Programming in the Programming Guide for a
detailed explanation.
Using an RF Transmitter Zone
A button type RF transmitter (5804) can be used to
provide access or egress for up to 4 doors. One button
will control one door. Also, a button can be used to
provide access or egress due to a panic or duress
condition.
An RF transmitter (5816) can be used with a remote
switch to provide exit in case of a fire alarm using a
PassPoint event action. To program the RF transmitter
for access control, perform the following steps:
Step
Action
1
Enter Zone Programming in the #93 Menu
Mode.
2
Program the zone with a response type 27
(Access Point).
3
Enter the access point number (00-31) of the
door.
4
Indicate whether RF device is for entry or exit.
5
Enter the partition number
6
Enter the input type: button RF (05).
7
Enter the loop number.
8
Enroll the serial number
See Zone Programming in the Programming Guide for a
detailed explanation.
Section 4 – Programming
4-9