This section describes the procedures for mounting and wiring the control panel and all the peripheral
devices.

Mounting the Control Cabinet

To mount the control cabinet, perform the following steps:
Step
Action
1
Before mounting the circuit board, remove the metal knockouts for the wiring entry that you will be using.
DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN
INSTALLED.
2
Using fasteners or anchors (not supplied), mount the control cabinet to a sturdy wall in a clean, dry area
that is not readily accessible to the general public. The back of the control cabinet has 4 holes for this
purpose.
To provide certificated burglary service for UL installations, refer to the special requirements and Figure 3-2
U L
Cabinet Attack Resistance Considerations to follow.

Installing the Cabinet Lock

Use an ADEMCO No. N6277 Cam Lock and No. P3422-
2 Clip for universal commercial cabinet. To install the
lock, perform the following steps:
Step
Action
1
Insert the key into the lock. Position the lock
in the hole, making certain that the latch will
make contact with the latch bracket when the
door is closed.
2
While holding the lock steady, insert the
retainer clip into the retainer slots.

Grade A Mercantile Premises Listing Guidelines

The panel door must be supervised. Mount the
clip-on tamper switch (supplied) to the cabinet's
right side wall as shown in the diagram below, and
wire it to one of the hardwire zones.
Use a bell with a tamper-protected housing such as
the ADEMCO AB12. The bell housing's tamper
switch and inner tamper linings must also be wired
to the hardwire zone.

Installing the Control

LOCKED
UNLOCKED
CABINET DOOR BOTTOM
Figure 3-1: Installing the Lock
Assign the tampers' hardwire zone to a burglary
partition. Program the hardwire zone for day
trouble/night alarm (zone type 5) when only one
burglary partition is used. Program it for 24-hr.
audible alarm (zone type 7) when more than one
burglary partition is used.
S E C T I O N
RETAINER CLIP
(NOTE POSITION)
RETAINER
SLOTS
RETAINER
CLIP
3
3-1