INSTALLATION PRECAUTIONS

The following precautions are mandatory for a safe installation.
(A) Compliance with local building codes and regulations is mandatory.
(B) Be careful not to damage the unit in handling and unpacking component parts and accessories.
(C) Model 80ZC Cabinet, use only 8"listed 2100º UL 103 HT TYPE Chimney with the 80ZC
Cabinet (ONLY AFTER) New Buck Corparation Stove 80 has been installed into the 80ZC
Cabinet.
(D) The chimney must extend a minimum of three feet (3') above the highest point where it penetrates
the roof (three feet (3') above a flat roof or up to a 2 /12 pitch roof ) and the chimney must extend a
minimum of two feet (2') higher than any portion of the building within ten feet (10') of the chim-
ney. The minimum height is fourteen and one half feet (14 1/2'). The maximum height is forty two
feet (42'). A two-inch (2") clearance must be maintained between the chimney and any combustible
materials at all points.
(E) A rain cap must be used to terminate the chimney to prevent down-draft. Use the factory approved
rain cap which is approved for the type chimney being installed.
(F) "DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER
APPLIANCE." DO NOT USE A FLUE INTENDED FOR A GAS APPLIANCE."DO
NOT CONNECT TO ANY DISTRIBUTION DUCT OR SYSTEM."
THE STRUCTURAL INTEGRITY OF THE HOME, FLOOR, WALL AND
(MOVE OPENING AND/OR REPOSITION HEATER LOCATION IF NECESSARY)
CAUTION
CEILING/ROOF MUST BE MAINTAINED.
Page 5