CONTINUED FRAMING AND INSTALLATION
FLOOR PROTECTOR OR FINISHED HEARTH EXTENSION WITH OPTIONAL RAISED BASE
You must use a non-combustible material or a UL listed floor protector R-Value 0.6 .( SEE FLOOR
PROTECTION Page 8) All the way against front of cabinet and a minimum of 16" in front of stove feed
door opening and 47 1/2" the width of the cabinet (See Figure 14)
Construct the hearth extension (floor protector or finished hearth) out of non-combustible inorganic
building materials as follows
a. The hearth extension must extend 16" from the stove feed door opening and against front of
80ZC cabinet. (See Figure 14).
b. The hearth extension width must be at least 47 1/2". (See Figure 14).
c. The hearth extension must be made of brick 2" thick or a listed "Floor Protector" or "Hearth
Extension" with R- value of: R=0.6 , or a hearth extension made of non-combustible inorganic
material with a K * factor of K=2.5 BTU ( (HR)(ft
WARNING:
Install the floor protector or finished hearth extension only as specified. The hearth
extension must be a minimum of 16" in front of the stove feed door opening and must be 47 1/2" wide
minimum. NOTE: Be sure to place safety shield under 80ZC and hearth protector or finished
hearth
NOTE:
No floor protector or finished hearth extension is needed directly under the Model 80ZC Cabi-
16"
FLOOR PROTECTOR OR FINISH HEARTH EXTENSION
2
)(F/in.) (See Page 8)
FIGURE 14
47 1/2"
Page 15
SAFETY SHIELD
BENT 90˚
UNDER FLOOR
PROTECTOR