Step 4. Attach and Cable Secondary Rack (If Ordered)

Use the illustration on page 10 for more information on following these procedures.
1. Screw two standoffs to the primary rack and the other two to the secondary rack.
2. Attach bottom EMC trim (part number 11P2872) to the secondary rack, using four
screws.
3. Place lower vertical trim foam on the secondary rack, starting at the bottom EMC
trim.
4. Place top vertical foam on top of the bottom foam.
5. Place the top EMC trim (part number 11P1105) on top of the secondary rack, using
the middle two screws. Do not tighten the screws yet.
6. Place the two vertical EMC trim panels (part number 11P095) into position. The trim
panels are located so that the flanges point into the frame and fit on the tabs of the
bottom and top EMC trim.
7. Screw down the top EMC trim to lock in the vertical trim.
8. Roll the two frames together, being careful not to damage the EMC trim with the
standoffs.
Chapter 2. Installing the pSeries 690
9