Mqrb4436 Combustible Enclosure Heights - Marquis Infinite MQRB4436N Installation Instructions Manual

Infinite series zero clearance vented gas fireplace
Hide thumbs Also See for Infinite MQRB4436N:
Table of Contents

Advertisement

MQRB4436 Combustible Enclosure Heights

Cold Climate Recommendation
When installing this fireplace against an exterior wall or chase, it is recommended that the outer walls be
insulated to conform to applicable insulation codes. Drywall must be installed over vapor barrier and
insulation material to prevent direct contact with the appliance.
See Thru or Single Sided Installation
[Steel Stud Framing Shown]
Single Side Installation Only
[Steel Stud Framing Shown.]
For Propane Horizontal installations the venting must be a minimum of two
feet vertical off the flue before going horizontal.
7-3/4" Min for Natural Gas
24" Min for Propane
37-1/2" Min for Natural Gas
53-3/4" Min for Propane
7-3/4" Min for Natural Gas
24" Min for Propane
37-1/2" Min for Natural Gas
53-3/4" Min for Propane
The Wall Thimble Shield Z57WTS is required in
All Enclosures below 72" [Seventy-Two Inches].
Place Wall Thimble Shield Z57WTS against the
Wall Thimble Immediately above the Vent. Install
the Wall Thimble Shield using [3] DT Screws.
The minimum
vertical
installation height
must be adhered
to.
Flex pipe venting
must be fully
stretched.
Kingsman Flex
venting MUST be used
on the MQRB4436.
Use of DuraVent-
DirectVent Pro or
other hard pipe
Venting systems is
not permitted.
15