Wine Guardian Through-the-Wall Installation, Operation And Maintenance Manual page 35

Wine cellar cooling systems
Hide thumbs Also See for Through-the-Wall:
Table of Contents

Advertisement

Differential
temperature
adjustment
Deadband setting
Test mode setting
System Selection
Setting 16
Press "Mode" button to advance to Setting 16.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint.
This setting changes the system/compressor; turn
on temperature above setpoint. Factory default is
set to 1 Deg F.
Example: Sensor reading = 55 Deg F
Setting 16 Set to +3 Deg F
System/compressor turns on at 58 Deg F.
Setting 17
Press "Mode" button to advance to Setting 17.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint.
This setting is the minimal allowable temperature
difference between heating and cooling setpoints.
Maximum is 5 Deg F, minimum is 1 Deg F.
Factory default is set to 2 Deg F
Setting 18
Press "Mode" button to advance to Setting 7.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint. When set to one the
controller will automatically turn on all outputs
with the exception of electric heat. Factory
default is zero.
Zero (0) = Off
One (1) = On
Setting 19
DO NOT CHANGE
35