Wine Guardian Through-the-Wall Installation, Operation And Maintenance Manual page 33

Wine cellar cooling systems
Hide thumbs Also See for Through-the-Wall:
Table of Contents

Advertisement

Deg F or Deg C
Low temperature
alarm set point
Low humidity
alarm set point
High humidity
alarm set point
Add or remove
humidifier
Fan AUTO or ON
Advanced Settings
Setting 1
Press the "Down" arrow to change temperature
from Deg F to Deg C.
Press the "Up" arrow to change temperature
from Deg C to Deg F.
Setting 2
Press "Mode" button to advance to Setting 2.
Press the "Up" or "Down" arrow buttons to
adjust to the desired set point. Factory default
is 50 Deg. F.
Setting 3
Press "Mode" button to advance to Setting 3.
Press the "Up" or "Down" arrow buttons to
adjust to the desired set point. Factory default
is 65 Deg F.
Setting 4
Press "Mode" button to advance to Setting 4.
Press the "Up" or "Down" arrow buttons to
adjust to the desired set point. Factory default
is 5%.
Setting 5
Press "Mode" button to advance to Setting 5.
Press the "Up" or "Down" arrow buttons to
adjust to the desired set point. Factory default
is 95%.
Setting 6
Press "Mode" button to advance to Setting 6.
Press the "Up" or "Down" arrow buttons to
adjust to the desired set point. Factory default
is zero (0).
Zero (0) = No humidifier
Two (2) = Stand-alone remote mounted
humidifier
Setting 7
Press "Mode" button to advance to Setting 7.
Press the "Up" or "Down" arrow buttons to
adjust number to the desired set point. Factory
default is zero (0).
Zero (0) = Auto – fan only turns on when
there is a call for cooling or heating
One (1) = Fan On – fan remains on
continuously
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Through-the-wall wine cellar cooling systems

Table of Contents