Wine Guardian Through-the-Wall Installation, Operation And Maintenance Manual page 34

Wine cellar cooling systems
Hide thumbs Also See for Through-the-Wall:
Table of Contents

Advertisement

Advanced Settings-
Special access
required. Contact
Wine Guardian
Service Department
for access code
Compressor anti-
short cycling time
Set up remote
sensor
or thermostat
Room sensor
calibration
34
Setting 8
Press "Mode" button to advance to Setting 8.
Press the "Up" or "Down" arrow buttons to
adjust number to the access code. Press
"Mode" button to continue onto setting 9
through 19.
Setting 9
Press "Mode" button to advance to Setting 9.
Press the "Up" or "Down" arrow buttons to
adjust to the desired time in one minute
increments. Maximum is 10 minutes, minimum
is 0 minutes.
Compressor anti-short cycling time is the amount
of allowable time between compressor stop and
restart. Rapid start/stop of compressors can cause
premature failure. Factory default is 5 minutes.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT.
Setting 10
Press "Mode" button to advance to Setting 10.
Press the "Up" or "Down" arrow buttons to
adjust to the desired setting.
Remote sensor
Remote interface
Local interface – Through-the-wall unit only
Averaging – Jumper position within sensors
must be adjusted. See page 27.
Setting 15
Press "Mode" button to advance to Setting 15.
Press the "Up" or "Down" buttons to adjust to
the desired setpoint. Maximum setting is +5,
minimum setting is -5. Factory default is zero
(0). Sensor calibration setpoint changes the
actual display reading (temperature only) by
the value of this setting.
Example: Sensor reading = 55 Deg F
Setting 15 Set to +4
Display reading = 59 Deg F