Preparing for Operation
S Set the rated input current of the motor with n032 and the electronic thermal protective function
with n033 to determine the motor protective characteristics.
n032
Motor Rated Current
Setting range
See note 1
Note 1. The set value range is from 10% to 200% of the rated output current.
Note 2. The default-set value varies with the Inverter model.
Note 3. Be sure to set n032 after checking the rated input current of the motor.
n033
Electronic Thermal Protection Function Selection
Setting range
0 to 4
Set Values
Set value
0
No protection.
1
For standard motors with standard ratings (with a time constant of 8 min).
2
For standard motors with short-time ratings (with a time constant of 5 min).
3
For dedicated motors with standard ratings (with a time constant of 8 min).
4
For dedicated motors with short-time ratings (with a time constant of 5 min).
3-24
Unit
---
Unit
---
Description
Chapter 3
Default setting
1
Default setting
1