Operation
Data
Description
display
%pe6 Parameter setting error
Parameter settings other than
the ones used for
multi-function input and V/f
pattern settings were
improper.
Check whether the rated input current of the motor set with n032
satisfies the following condition. If not, check the rated current of
the motor and reset n032.
→ Rated input current of Inverter x 0.1 x n032 x rated input
current of Inverter x 2
Jumping frequency 1 set with n058 is higher than jumping
frequency 2 set with n059. Reset jumping frequencies 1 and 2 to
satisfy the following condition.
→ n058 x n059
The upper limit of the output frequency set with n030 is lower
than the lower limit of the output frequency set with n031. Reset
the upper and lower limits of the output frequency to satisfy the
following condition.
→ n030 y n031
Cause and action