Input Open-Phase Detection Level; Input Open-Phase Detection Time; Output Open-Phase Detection Level; Output Open-Phase Detection Time - Omron SYSDRIVE 3G3HV SERIES User Manual

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Preparing for Operation
• Select with n079 whether to permit the Inverter to protect the Braking Resistor Unit connected to the
Inverter from overheating.
• The Inverter will display an error and turn OFF the output power when the Inverter detects the over-
heating of the Braking Resistor Unit with the RH signal if n079 is set to 1.
Set Values
Set value
0
Inhibits overheating protection from functioning.
1
Permits overheating protection to function.
n080

Input Open-phase Detection Level

Setting range
1 to 100
n081

Input Open-phase Detection Time

Setting range
2 to 255
• The parameters n080 and n081 are used to set the input phase loss detection function.
• It is usually not necessary to change the default-set values.
• The Inverter will not detect input phase loss if n080 is set to 100.
• Set n080 of the 200-V Inverter based on 400 VDC as 100% and that of the Inverter of 400-V class
based on 800 VDC as 100%.
• The input phase loss detection function is used to detect the voltage ripples that will be generated from
the main circuit DC power supply when input phase loss results.
The Inverter will detect input phase loss if the voltage width of the voltage ripples of the main circuit DC
power supply exceeds the range set with n080 for a period exceeding the time set with n081.
• If the power supplied to the Inverter has ripples, set n080 or n081 to a large value so that the Inverter
will not detect input phase loss.
n082

Output Open-phase Detection Level

Setting range
0 to 100
n083

Output Open-phase Detection Time

Setting range
0.0 to 2.0
• The parameters n082 and n083 are used to set the output phase loss detection function.
• The Inverter will not detect output phase loss if n082 is set to 0. The default-set value of n082 is 0.
• When an output phase loss occurs, the Inverter will detect a decrease in the output current of the
phase.
• To use the output phase loss detection function, refer to the following procedure and set with n082 an
appropriate output phase loss detection level.
1. Start the motor with no load.
2. Use the Digital Operator and monitor the amperage of the output current.
Description
Unit
(400/800 VDC
as 100%)
Unit
x 1.28 s
Unit
% (Rated output
current ratio)
Unit
s
Chapter 3
Default setting
7
Default setting
8
Default setting
0
Default setting
0.2
3-89