Installation
D Round Solderless Terminals and Tightening Torque
Wire thickness
2
(mm
)
0.5
0.75
1.25
2
3.5/5.5
8
14
22
30/38
50/60
80
100
100
150
200
325
Note Determining Wire Size
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated volt-
age.
Line voltage drop is calculated as follows:
Line voltage drop (V) = √3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10
2-20
Terminal
Size
screw
M4
1.25 – 4
M4
1.25 – 4
M4
1.25 – 4
M4
2 – 4
M5
2 – 5
M6
2 – 6
M8
2 – 8
M4
5.5 – 4
M5
5.5 – 5
M6
5.5 – 6
M8
5.5 – 8
M5
8 – 5
M6
8 – 6
M8
8 – 8
M6
14 – 6
M8
14 – 8
M6
22 – 6
M8
22 – 8
M8
38 – 8
M8
60 – 8
M10
60 – 10
M10
80 – 10
100 – 10
M12
100 – 12
150 – 12
200 – 12
M12 x 2
325 – 12
M16
325 – 16
Tightening
torque (NSm)
1.2
1.2
1.2
1.2
2.0
2.5
6.0
1.2
2.0
2.5
6.0
2.0
2.5
6.0
2.5
6.0
2.5
6.0
6.0
6.0
10.0
10.0
10.0
14.0
14.0
14.0
14.0
25.0
Chapter 2
–3