DSC PowerSeries PC1404 V1.1 Installation Manual page 6

Dsc power series security systems installation guide
Table of Contents

Advertisement

SIA-FAR Minimum System
Applicable UL Standards
UL 985 Household Fire Warning System Units
Requirements:
UL1023 Household Burglar Alarm System Units
1 PC1404 Panel
UL 1635 Digital Alarm Communicator System Units
1 Local annunciation devices
ANSI/SIA CP-01-2010
Local annunciation devices may be
any combination of these keypads:
PK5500, PK5501, PK5508, PK5516,
PC1404RKZ, LCD5511, LED5511Z,
PC1555RKZ
Battery capacity for 4 h standby is
at least 4 Ah. Battery capacity for 24 h
standby is 7 Ah. (Max. Aux current shall
BLK
be in accordance with Section 2.2 battery
connection.) Recommended batteries:
DSC BD4-12 or DSC BD7-12.
For NA
Use a UL/CSA-listed Class 2 Transformer
16.5V
40 VA DSC PTD 1640U (USA)/
installations
AC
PTD 1640 (CDN).
only
D
not connect transformer to
O
receptacle controlled by a switch.
Note: It is the installer's responsibility to
For EU
ensure that the external PRIMARY wires
installations
are tied together using a cable tie or
only
equivalent as close as possible
to the terminal block.
ZONE DOUBLING
1500
2400
- 49
(32 120 F)
-
0
85
Refer to the Installation Guide (29008503) and User Manual (29008622) for complete
operating instructions.
is UL listed
1404
PC1404 Wiring Diagram
4.0/7.0 Ah
CON1
BAT+BAT-
200–350 mA
RED
(NA)
230/240 V AC
(EU)
50/60Hz
FUSE 315mA/250V
(within terminal block)
LCD5511
LED5511
PC1555RKZ
PK5500/PK5501
PK5508/PK5516
PC1404RKZ
.
(for UL/ULC applications)
so s
I
-
-
-
T-1
R-1
TIP
RING
2-WIRE SMOKE DETECTORS
o
4-WIRE SMOKE DETECTORS
RM-1/RM-2 POWER LOOP
SUPERVISORY RELAY
12V
EOLR-2
END-OF-LINE
RESISTOR
5600 Ohm, 0.5W
(a) The delay (power-up) time marked on the installation wiring diagram of the smoke detector
or on the installed smoke detector(s) is to be used. Control panel is suitable for the following
UL installations:
Installation Type
Signalling Means
Resi Fire Burg
DACT
US: F53AL01BPC1404
IC:160A-PC1404
In Canada, the PC1404 is listed for Residential Fire and Burglary installations. The product
shall be installed as per UL-S540 and ULC-S310 Standards.
WARNING: Incorrect connection of batteries may result in battery rupture or
fire hazard. Do NOT allow metal objects to connect the positive and
negative terminals. Ensure that batteries are connected with correct polarity
[Red to (+), Black to (-)]. Failure to comply with this may result in battery
rupture and/or fire hazard.
THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE THAT WILL RESULT IN A
DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE
TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE
CIRCUITS UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
Note: Alarm Verification is not supported for 2-wire interface, only 4-wire.
v
Test the alarm system at least
once per week.
UL
AUX Wiring
Use No. 14-22 AWG conductor.
Total current draw from keypads,
PGM outputs and AUX circuits must
not exceed 550mA.
.
BRN
Telephone line wiring
GRA
GRN
RED
RJ-31X
26 AWG
30
2200 Ohm
NAME
MODEL
COMPATIBILITY ID
END-OF-LINE
RESISTOR
DSC
FSA-210B Series
FS200
EOLR-3
NOTE: Refer to the FSA-210 Installation Manual for more details.
UL compatibility ID for FSA-210B
series is FS200; for ULC listed
installations, use FSA-210A and
FSA-410A series.
DC
ALARM
INITIATING
LOOP
RESISTANCE
100 Ohm
-31X
REFER TO
MANUAL FOR
LIST OF
COMPATIBLE
DEVICES
PC14-1
13.7
24
MAX #
BASE
SEE NOTE
NONE