DSC PC1832 Reference Manual
Hide thumbs Also See for PC1832:
Table of Contents

Advertisement

PC1616 / PC1832 / PC1864
This manual contains information on limitations regarding product use and function and information on the limitations as to liability
of the manufacturer. The entire manual should be carefully read.
Reference Manual
PC1616/PC1832/PC1864 v4.1
DLS2002 and higher

Advertisement

Table of Contents
loading

Summary of Contents for DSC PC1832

  • Page 1 PC1616 / PC1832 / PC1864 This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully read. Reference Manual PC1616/PC1832/PC1864 v4.1 DLS2002 and higher...
  • Page 2: Table Of Contents

    Section 1: Introduction PC1616/PC1832/PC1864 Device Ratings..6 System Output Ratings ......7 1.1 About the PC1616/PC1832/PC1864 System .
  • Page 3 [*][6] User Functions ......15 5.5 Communicator Programming ....35 LCD Keypad User Functions .
  • Page 4 [996][Installer Code] - Restore PC5132 Wireless Factory B.1 PC1616/PC1832/PC1864 UL/ULC Wiring Diagram ..58 Default Programming ......49 B.2 PC1616/PC1832/PC1864 Standard Wiring Diagram .
  • Page 5: Section 1: Introduction

    • B (self powered warning device and internal dialer required), User Guide • D (use of DSC model T-Link TL250 encrypted Ethernet com- One user guide comes with the PC1616/PC1832/PC1864 sys- municator required). tem. The User’s Guide provides easy to follow instructions for The PC1616/PC1832/PC1864 are high end security systems.
  • Page 6: Memory

    System Supervision Features • AUX Output Voltage: 12V -15%/+10% when AC Input The PC1616/PC1832/PC1864 continuously monitors a number of Voltage is 85% to +110% of rated value and output current possible trouble conditions and provides audible and visual indi- is 500mA (700mA for UL/ULC) (550mA for IMQ) cation at the keypad.
  • Page 7: Additional Devices

    PC5108 v1.0 and lower modules can only support the first PC5700/PC5720 Fire Module 32 zones on the PC1616/PC1832/PC1864 system. PC5108 v1.0 and lower modules enroll as two modules and use up two supervisory This is a zone expansion fire module that can be used for ULC slots.
  • Page 8: Enclosures/Cabinets

    NOTE: 102mm / 42.75” x 14.25” x 4.0” When two batteries are required in order to meet the min- imum standby times, the DSC Enclosure Model Power UC1 shall be PC4050C Description: Alternate Main Control Cabinet (UL/ULC Household Fire & ULC Commercial Burglary) for the used (for European Installations only).
  • Page 9: Section 2: Installation And Wiring

    Section 2: Installation and Wiring The following section provides a description of how to wire and the options function. The Programming Worksheets should be configure devices and zones. filled out completely before attempting to program the system. Step 11 Testing the System 2.1 Installation Steps The following steps are provided to assist with the installation of Test the panel completely to ensure that all features and functions...
  • Page 10: Programmable Outputs - Pgm1 To Pgm4

    2.5 Current Ratings - Modules & Accessories phone lines intended for use with a FAX machine. These lines may In order for the PC1616/PC1832/PC1864 system to operate prop- incorporate a voice filter which disconnects the line if anything erly, the power output capabilities of the main control and expan- other than FAX signals are detected, resulting in incomplete trans- missions.
  • Page 11: System Output Ratings

    8 Zone LED Keypad With Wireless 135mA Module NOTE: PC5108 v1.0 and lower modules can only support the first 32 zones on the PC1616/PC1832/PC1864 system. PC5108 v1.0 and RFK5516 16 Zone LED Keypad With Wireless 135mA Module lower, PC5700 enrolls as two expander modules.
  • Page 12: Function Key Programming

    • 1st digit - enter 0 for Global operation, or enter 1-8 for If a module is connected but does not show as being present, it may be due to any of the following reasons: Partitions 1-8 • it is not connected to the Keybus •...
  • Page 13: Single End Of Line (Eol) Resistors

    NOTE: The maximum number of smoke detectors on the 2-wire If the PC1616/PC1832/PC1864 is set up for Double loop is 18. Refer to the ‘2-Wire Smoke Detector Initiating Circuit’ table below. End of Line (DEOL) resistors the panel will detect both Fault and Tamper (Short and Open) conditions as tamper condition.
  • Page 14: Compatible 2-Wire Smoke Detectors

    NOTE: Refer to smoke detector installation sheet when position- PK55XX/RFK55XX ing detectors. PK55XX/RFK55XX keypad comes with a Z/P terminal. This termi- Compatible 2-Wire Smoke Detectors nal can be configured as an input (zone) or output (PGM). To connect the zone input on a PK55XX/RFK55XX keypad, run Model Model Model...
  • Page 15: Section 3: How To Program

    Section 3: How to Program The following section of the manual describes how to enter NOTE: You must view the Ready light. If the light is flashing, any number you enter will be programmed as the HEX equivalent. Installer Programming and how to program the various sections. Example: To enter ‘C1’...
  • Page 16: Section 4: Keypad Commands

    Away button. cate alarm status to the user. The PC1616/PC1832/PC1864 If a delay zone is violated during the exit delay (e.g. somebody User’s Guide provides basic directions for arming and disarming...
  • Page 17: Event Buffer (Event Log)

    Enter a valid Access Code at the keypad. If an error is made, re- 2. Enter the two-digit number of the zone(s) to be bypassed (01- enter the code correctly. When a correct code is entered the key- 64). On LED keypads, the zone light will turn on to indicate that pad will turn off the ‘Armed’...
  • Page 18: Alarm Memory

    Light Trouble Light [1] Service Required: Press [1] to determine the specific trouble. Lights 1 - 8 will light up to indicate the trouble: • Light [1] Low Battery: Main panel backup battery charge is low (below 11.5 volts under load).Trouble is restored when the battery charges over 12.5 volts.
  • Page 19: Installer's Programming - Codes And Options

    If the Master Code Not Changeable option is enabled the Sys- Programmable Attributes tem Master Code can only be changed using Installer Program- Attribute Description ming. For Future Use For Future Use NOTE: For EN installations the installer will not have access Zone Bypass enabled.
  • Page 20: Lcd Keypad User Functions

    To program user functions, perform the following: dition for the violated fire zone. To provide support for event com- 1. Press [*][6][Master Code]. The keypad will flash the ‘Pro- munication new Programming Sections are added for the Walk Test Begin/End reporting codes. gram’...
  • Page 21: Function Keys

    (see section ’[*][5] 4.3 Function Keys Programming Access Codes’). There are 5 function keys on the PC1616/PC1832/PC1864 key- pads. The function is activated by pressing and holding the key [12] - [*]+[6] User Functions for 2 seconds.
  • Page 22: Global And Partition Keypad Operation

    1. With the PK5500/RFK5500 series keypads press [*][2], when seconds. The keypad will go blank. The user must then press and hold one of keys [1] - [8] for two seconds, depending on which Trouble 8 appears on the screen, press the [*] key. This will partition they want to access (e.g.
  • Page 23: Section 5: Programming Sections

    Section 5: Programming Sections The structure of this section corresponds with the structure of the Programming Worksheets (PWS) and is intended to be used with them. 5.1 Keypad Programming Refer to Section 2.7 ‘Keypad Assignment’ 5.2 Basic Programming [001]-[004] - Zone Definitions NOTE: In addition to selecting how each zone will operate, attributes may be programmed by zone (see section 5.3 ’Advanced...
  • Page 24: System Times

    Option Zone Type Description Maintained Keyswitch A keyswitch module may be connected to the zone programmed as Maintained Keyswitch arm. In the restored state, the panel is disarmed. Only the violation of this zone type to the alarm state will make the panel arm. Tampers and Faults will only initiate their respective trouble sequence.
  • Page 25: Installer's Code

    The siren will silence after the number of minutes programmed for • The first two entries of Section [010] are used to program the Bell Cut-off time have passed. The default Bell Cut-off is 4 the last two outputs on the PC1832/PC1864, and the first minutes two on the PC5208.
  • Page 26 [009]-[011] - Programmable Output Options Option Output Description Burglary and Fire Bell Fol- This output will activate when the alarm output is active (switch to ground) and will turn off when the alarm output is lower silenced. If the alarm output is pulsing, the PGM output will pulse as well. This PGM output will follow: •...
  • Page 27 Option Output Description TLM and Alarm This output will activate (switch to ground) when a telephone line fault condition is present AND an alarm occurs. The output will remain active until an access code is entered to disarm any partition. The output will activate for all audible and silent alarms (except duress) if a TLM trouble is present.
  • Page 28: Keypad Lockout Options

    Option Output Description Zone Follower Output This output type is normally active and allows an output to deactivate for the duration that a zone is violated. The PGM Attributes are an eight-bit toggle mask that selects which zones the output will follow. Example: If PGM 1 is pro- grammed as Type [29] with Attributes 1, 6, and 8 on, the Output will turn off when any one of Zones 1, 6, or 8 are in violation, and will activate when all three zones are restored.
  • Page 29: Second System Option Codes

    Option Definition On/Off Description Single End-of-Line Resistors All zones must have a 5.6KΩ resistor across them. If the zone is shorted or open, it will be in the violated state. If the zone is open and programmed as a fire zone, it will be in the trouble state.
  • Page 30: Third System Option Codes

    Option Definition On/Off Description Bell Squawk On Bell Squawk On Entry Delay The Bell output will pulse with the same timing as the buzzer during the Entry Entry Delay time. The bell will also sound 3 squawks per second for the final 10 seconds if Option 6 in this section is enabled.
  • Page 31: Fourth System Option Codes

    NOTE: This option must be ON when using a PC5132 older than v3.00. NOTE: When using wireless keys with access codes, if you default the PC1616/PC1832/PC1864, you should also default the PC5132 (See Section 5.12 Special Installer Functions [996]).
  • Page 32: Sixth System Option Codes

    Option Definition On/Off Description Audible RF Jam Audible RF Jam Trouble Beeps Keypads will sound trouble beeps when an RF Jam Trouble is detected. Trouble Beeps An RF Jam will not sound Trouble Beeps Keypads will not sound trouble beeps when an RF Jam Trouble is detected.
  • Page 33: Seventh System Option Codes

    Option Definition On/Off Description Cross Zone/Police Cross Zoning is Enabled The panel will use the Cross Zone Attribute for Burglary Verification. Code This feature requires two or more trips on a zone(s) specified as “cross zones” within a specified time before starting an alarm sequence.
  • Page 34: Keypad Zone Assignment

    Option Definition On/Off Description Remote Reset After Remote Reset After Second Activation Only A remote reset will occur only after a second confirmed Second Activation alarm, which is generated by the activation of a different zone, or the same zone with double hit enabled. This second activation must tie in with the Burglary verified timer.
  • Page 35 Option Definition On/Off Description Remote Reset Remote Reset Enabled. The purpose of this feature is to force the end user to contact the Installer/Cen- tral Station whenever they have an alarm condition. This is accomplished by locking out the panel after an alarm occurs, which will force the end user to call the Installer/Central Station to get a Reset code which must be entered on the keypad before they will be able to use their system.
  • Page 36: Tenth System Option Codes

    [022] - Ninth System Option Codes Option Definition On/Off Description Access Code Access code is required for [*][1], [*][2] and [*][3] menu options In order to access the [*][1] bypass Required for [*][1], menu, [*][2] trouble menu, or [*][3] alarm memory menu a valid access code is required. Events will also be [*][2], [*][3] generated and logged, thus identifying the user.
  • Page 37: Fast Loop Response

    005. Valid entries are 001-005. • Enter Programming Section [168] when setting the clock NOTE: The PC1616/PC1832/PC1864 will not allow more than 5 dialing attempts to a single phone number. If a value higher than forward 5 is programmed in Section [165], the panel will still only dial 5 •...
  • Page 38: Pgm Output Timer

    expires, the Police Code will not be logged or transmitted, Example 2 : 1st Sunday in March, 2:00am and the timer will restart. Ex. 2 • If the Cross Zone Attribute is used, the first zone alarm will Month valid entries 001-012 not log or transmit.
  • Page 39: Partition & Zone Programming

    You can create up HEX (F)- end of telephone number marker to eight partitions on the PC1616/PC1832/PC1864 system. To set up the system for more than one partition, you must turn on 3rd telephone Number Enable ..Section [380], Option [5] each partition in section [201].
  • Page 40: Partition 1-8 Account Codes

    NOTE: SIA will use this account code for all Partitions and System Burglary Not Verified : this reporting code will be sent after the Events! System events will be identified by Nri0, with Partitions 1-8 burglary verified timer expires after a zone alarm occurs. using Nri1-8.
  • Page 41: Opening (Disarming) Reporting Codes Ac- Cess Codes 1 To 32

    [342]-[343] - Opening (Disarming) Reporting Codes Access Fire Trouble Restoral: the Fire Trouble Restoral Reporting Code will be transmitted when the correct resistance value is measured Codes 1 to 32 on any Fire type zone. The panel will transmit an Opening Reporting Code to indicate Auxiliary Power Supply Trouble Restoral: the panel constantly...
  • Page 42: Pc5700 Maintenance Reporting Codes

    Contact ID option is not selected, reporting codes must be pro- • Fire Supervisory (Wireless/AML Zones 1-32) grammed. The 2-digit entry determines the type of alarm. The • TLM Trouble (PC1616/PC1832/PC1864, PC5700 Line 1-2) panel will automatically generate all other information, including the zone number.
  • Page 43: Residential Dial

    The Communicator Call Direction Options can be used to disable Hex [A] - not used reporting of events such as Openings/Closings. Also, if all the Hex [B] - simulates the [] key on a touch tone telephone Opening/Closing reporting codes were programmed as [00] the Hex [E] - two second pause panel would not report.
  • Page 44: Robofon Format

    Example: If you program the zone 3 alarm reporting code as [31], • 0 = Talk/Listen Audio Event (any event type) the panel will send event code 1 in channel 3. The panel will send • 1 = New Event (Alarm, Tamper, Trouble, etc.) the number 5 for each of the other channels, so that the event •...
  • Page 45: Communication Variables

    [377] - Communication Variables Communication Variables Swinger Shutdown (Alarms & Restores) This value defines the number of attempts (alarm and restore pairs) per zone that the panel will log and communicate before it shuts down for that zone (“swinger shutdown”). Valid entries are 000 to 014. Different limits can be programmed for Zone Alarms, Zone Tampers and Maintenance signals.
  • Page 46: First Communicator Option Codes

    or communicated if the panel does not get through to the DLS grammed value is first converted to decimal (00 - 99). If the origi- computer. nal HEX value was greater than 99 in decimal it will rollover to 00 The calculation of the Time of Day to call is carried out by genera- and continue (ex.
  • Page 47: Second Communicator Option Codes

    [381] - Second Communicator Option Codes Option Communicator Code On/Off Description Opening After Alarm Keypad Opening After Alarm Keypad Ringback Enabled When the Opening After Alarm reporting code Ringback is successfully transmitted to a programmed telephone number, the keypad will sound a series of 8 beeps to confirm to the end user that the Opening After Alarm Code was sent and received.
  • Page 48: Downloading Options

    Option Communicator Code On/Off Description T-Link T-Link Interface Enabled The panel will communicate with a T-Link module connected to the PC- Link header. NOTE: Not investigated by UL. T-Link Interface Disabled The T-Link interface is disabled. AC Failure Transmission AC Failure Transmission Delay is in Hours The AC Fail Transmission delay is in hours (Section Delay [377], Option 5) AC Failure Transmission Delay is in Minutes The AC Fail Transmission delay is in minutes (Section...
  • Page 49: Downloading Computer's Phone Number

    Option Downloading Code Description DLS Window User Can Enable DLS Window. The user can use the [*][6][Master Code][5] Command to enable a 6 hour window in which the panel will answer calls for downloading if a successful Double Call routine is detected.
  • Page 50: Pgm Partition Assignment

    • Calculate the average amount of time per day that the panel gains or loses. The PC1616/PC1832/PC1864 has a 8-bit toggle field per output that determines which partitions the output is assigned to (outputs • Add or Subtract this value (seconds) from 60 and enter the PGM 1-14).
  • Page 51: First International Option Codes

    [701] - First International Option Codes Option International Code ON/OFF Description 50 Hz AC The incoming AC power cycles at 50 Hz. 60 Hz AC This is the North American standard where the incoming AC power cycles at 60 Hz. Time Base The timebase is the internal crystal oscillator.
  • Page 52: Delay Between Dialing Attempts

    Option International Code On/Off Description FTC Bell Bell on FTC when armed If a Failure to Communicate Trouble is generated while the system is armed, the Bell output will sound for the length of Bell time-out or until the system is disarmed. FTC Trouble only when armed If a Failure to Communicate Trouble is generated while the panel is armed, the Bell output will not sound but the keypad buzzer will sound trouble beeps until a key is pressed.
  • Page 53: For Future Use

    3. Enter the Installer Code. When this section is successfully entered, all programming in the 4. Enter section [990] again. PC1616/PC1832/PC1864 will be returned to the factory defaults. The programming for the ESCORT(TC), PC5132, PC5400 and [991][Installer Code] - Installer Lockout Disable PC59XX modules will not be defaulted.
  • Page 54: Section 6: Fire Monitoring

    This section explains all Fire monitoring zones that can be pro- tors can be programmed as Standard Fire. For residential appli- grammed on the PC1616/PC1832/PC1864 and PC5700 fire mod- cations, the zone can be programmed as Standard Fire. ule. Instructions on zone programming are located in the PC1616/ Power for the 4-wire smoke detectors can be derived from the aux- PC1832/PC1864 Installation Manual, see Partitions and Zones.
  • Page 55: Manual Sensor Reset ([*][7][2]) (Residential Use Only)

    The Sensor Reset function is designed so that the user can man- An AC Fail Trouble is generated if the AC fails on the PC1616/ PC1832/PC1864. AC Troubles are grouped for common indica- ually reset latching smoke detectors by entering [*][7][2]. In order for this feature to function, the detectors to be reset must be con- tion on a remote annunciator as an ‘AC Trouble’.
  • Page 56 Panel Bell Trouble* – This code will be sent when a bell Trouble Installation Manual, section 5.6, ‘Communicator Programming’, occurs. This is when an open circuit is detected across the bell [377] Communication Variables). terminals. When the Trouble condition is restored, the Main Bell Periodic Test TBL –...
  • Page 57: Section 7: Listing Requirements

    (DSC Model CMC-1 or PC4050CAR). Minimum requirement system for SIA-FAR Installations: All Commercial Installations • 1 PC1616/PC1832/PC1864 Control panel • The Entry Delay must not exceed 120 seconds • 1 Local annunciation device • The Exit Delay must not exceed 120 seconds.
  • Page 58 NOTES • Programming at installation may be subordinate to other UL requirements for the intended application. • Cross zones have the ability to individually protect the intended area (e.g., motion detectors, which overlap). • Cross zoning is not recommended for line security Installa- tions nor is it to be implemented on exit / entry zones.
  • Page 59 PC1616/PC1832/PC1864 Installer Programming Quick Reference Chart SIA CP-01 False Alarm Reduction SIA Feature Comments Range/Default Requirement Programming Section Exit Time Access to Entry and Exit delays for each partition and Bell Time Out for the system For Full or auto arming:...
  • Page 60: Appendix A: Reporting Codes

    Opening (disarming) using one of the following methods: key- (4) AA OP-00 switch, maintenance code, DLS software, wireless key [345]-[346] Battery Trouble/Rest. PC1616/PC1832/PC1864 battery is low/battery restored MA/R (3) A2 YT-00/YR-00 [345]-[346] AC Line Trouble/Rest. AC power to control panel is disconnected or interrupted/AC...
  • Page 61: Contact Id Zone Alarm/Restoral Event Codes

    Automatic Dialer SIA Auto Rep Section # Reporting Code Code Sent When... Contact ID Direction* Codes** Codes [345] TLM Failure Telephone line monitoring trouble MA/R (3) 51 LT-01 [346] TLM Restore Telephone line restored MA/R (3) 51 LR-01 [345]-[346] Gen System Trouble/Rest. “Service Required”...
  • Page 62: Appendix B: Wiring Diagrams

    FS200 SEE NOTE NONE NOTE: Refer to the FSA-210 Installation Manual for more details. 4-WIRE SMOKE DETECTORS Smoke detector must be latching type (ex. DSC FSA-410B Series) IMPORTANT: Minimum 6.4mm (1/4”) To reset smoke detector, enter [ ✱ ][7][2] separation must be maintained between...
  • Page 63: Pc1616/Pc1832/Pc1864 Standard Wiring Diagram

    B.2 PC1616/PC1832/PC1864 Standard Wiring Diagram North America Only POWER LIMITED Stand Off PC Board 1. Insert Stand off into cabinet mounting hole in the Cable Tie (not supplied) recommended desired location. Snap-in- place. Cabinet 2. Position circuit board mounting holes over UA503 Primary:120VAC/60Hz.
  • Page 64: Pc1616/Pc1832/Pc1864 European Wiring Diagram

    B.3 PC1616/PC1832/PC1864 European Wiring Diagram 1. Insert Stand off into cabinet 1. Insert Stand off into cabinet PC Board PC Board Stand Off Stand Off mounting hole in the desired location. mounting hole in the desired location. Snap-in-place. Snap-in-place. 2. Position circuit board mounting holes 2.
  • Page 65: Hardware Installation

    These terminals supply 700mA of current at 12V for commercial BELL/SIREN installations and 11.1-12.6 V for residential installations (e.g.DSC NOTE: Bell output is current lim- 700mA (max.) SD-15 WULF). To comply with NFPA 72 Temporal Three Pattern ited by 2A PTC...
  • Page 66 • Maximum number of 2-wire Smoke Detectors ....18 2-wire Smoke Detectors 4-wire Smoke Detectors Compatibility ID For FSA-210 Series is: FS200 Compatible DSC 2-wire smoke detectors: Compatible DSC 4-wire smoke detectors: FSA-210A Series for ULC FSA-410A Series for ULC...
  • Page 67 Program Section [701] Opt[7] to ON, if 14AH or 24AH battery is used. NOTE: Replace batteries every 3-5 years, If two batteries are required to meet the standby time, use DSC Enclosure Model Power UC1. Battery capacity will deteriorate with age and number of charge/discharge cycles.
  • Page 68: Pc1616/Pc1832/Pc1864 And Pc5700 Fire Module Communications Connections

    Do not combine the 2-wire smoke detector and 4-wire smoke detector on PGM2 (only 2-wire smoke detectors on NOTE: For devices requiring more than 50mA, use a relay (DSC RM- PGM2). 1) or UL-recognized parts only for this application. NOTE: The RM-1 relay module cannot be installed outside of the main panel enclosure.
  • Page 69 I n d e x 200 Baud FSK Door Chime Keypad Tampers Second System Option Codes 2-Wire Smoke Reset Double End of Line Resistors Keypad Zone Assignment 4-Wire Smoke Detector Zones Double Hit Keypad Zones Sensor Reset Downloading Option Codes, Keyswitch Zone Wiring Settle Delay Timer First...
  • Page 70: Limited Warranty

    Installer’s Lockout Warning Devices Any products returned to DSC which have the Installer’s Lockout option enabled and exhibit Warning devices such as sirens, bells, horns, or strobes may not warn people or waken someone no other problems will be subject to a service charge.
  • Page 71 Notes...
  • Page 72: Fcc Compliance Statement

    The REN is used to determine the number of devices that may be connected to a telephone line. PC1832 Registration number ......IC: 160A-PC1832 Excessive RENs on a telephone line may result in the devices not ringing in response to an incom- PC1616 Registration number .

This manual is also suitable for:

Pc1864Pc1616

Table of Contents