Warning Codes - Hitachi SJ700B Series Instruction Manual

Sj700b series inverter
Hide thumbs Also See for SJ700B Series:
Table of Contents

Advertisement

Chapter 5 Error Codes

5.2 Warning Codes

The following table lists the warning codes and the contents of parameter readjustments:
Warning code
001/ 201
Frequency upper limit setting (A061/A261)
002/ 202
Frequency lower limit setting (A062/A262)
004/ 204/ 304
Base frequency setting (A003/A203/A303) (*1)
Output frequency setting (F001), multispeed 0
005/ 205/ 305
(A202/A220/A320) (*2)
006/ 206/ 306
Multispeed 1 to 15 settings (A021 to A035)
009
Home search speed setting (P015)
012/ 212
Fequency lower limit setting (A062/A262)
015/ 215
Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
016/ 216
Multispeed 1 to 15 settings (A021 to A035)
019
Frequency upper limit setting (A061/A261)
021/ 221
025/ 225
Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
031/ 231
Frequency upper limit setting (A061/A261)
032/ 232
Fequency lower limit setting (A062/A262)
035/ 235/ 335
Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
036
Multispeed 1 to 15 settings (A021 to A035)
037
Jog frequency setting (A038)
Output frequency setting (F001), multispeed 0
085/ 285/ 385
(A202/A220/A320) (*2)
086
Multispeed 1 to 15 settings (A021 to A035)
091/ 291
Frequency upper limit setting (A061/A261)
092/ 292
Fequency lower limit setting (A062/A262)
095/ 295
Output frequency setting (F001), multispeed 0
(A202/A220/A320) (*2)
096
Multispeed 1 to 15 settings (A021 to A035)
Free-setting V/f frequency (1) to (6) (b100, b102, b104, b106,
b108, b110)
Free-setting V/f frequency (2) to (6) (b102, b104, b106, b108,
b110)
Free-setting V/f frequency (1) (b100)
Free-setting V/f frequency (3) to (6) (b104, b106, b108, b110)
Free-setting V/f frequency (1) (2) (b100, b102)
110
Free-setting V/f frequency (4) to (6) (b106, b108, b110)
Free-setting V/f frequency (1) to (3) (b100, b102, b104, b110)
Free-setting V/f frequency (5) (6) (b108, b110)
Free-setting V/f frequency (1) to (4) (b100, b102, b104, b106)
Free-setting V/f frequency (6) (b110)
Free-setting V/f frequency (1) to (5) (b100, b102, b104, b106,
b108)
Free setting, electronic thermal frequency (2) (3) (b017/b019)
Free setting, electronic thermal frequency (1) (b015)
120
Free setting, electronic thermal frequency (3) (b019)
Free setting, electronic thermal frequency (1) (2) (b015/b017)
The inverter displays a warning code when the data set as a target function code satisfies the condition (specified in
the Condition column) in relation to the data set as the corresponding basic function code.
Each parameter (target function code) is readjusted to the data set as the basic function code (by updating at the
inverter start-up).
*1
In this case, the base frequency is rewritten at parameter readjustment. If the base frequency is updated to an
inappropriate value, a motor burnout may result. Therefore, if the warning is displayed, change the current base
frequency data to an appropriate value.
*2
These parameters are checked, even when the digital operator (02) is not specified for the frequency source
setting (A001).
*3
The current value of the jump (center) frequency is updated to "'the current value of the jump frequency' - 'value of
the Jump (hysteresis) frequency width (minimum)'".
Target function code
5 - 10
Condition
Basic function code
Maximum frequency setting
(A004/A204/A304)
Frequency upper limit setting
(A061/A261)
Home search speed setting
(P015)
Fequency lower limit setting
(A062/A262)
Start frequency adjustment (b082)
Jump (center) frequency settings
<>
1/2/3 ± " Jump (hysteresis)
frequency width settings 1/2/3"
A063 ± A064, A065 ± A066,
<>
A067 ± A068 (*3)
Free-setting V/f frequency (7)
(b112)
Free-setting V/f frequency (1)
(b100)
Free-setting V/f frequency (2)
(b102)
Free-setting V/f frequency (3)
(b104)
Free-setting V/f frequency (4)
(b106)
Free-setting V/f frequency (5)
(b108)
Free-setting V/f frequency (6)
(b110)
Free setting, electronic thermal
frequency (1) (b015)
Free setting, electronic thermal
frequency (2) (b017)
Free setting, electronic thermal
frequency (3) (b019)

Hide quick links: