Chapter 4 Explanation of Functions
Intelligent output terminals
14
13
12
11
AC3
AC2
AC1
AC0
1
1
0
1
1
1
1
0
1
1
1
1
Item
Alarm code output

4.2.66 Logical output signal operation function (LOG1 to LOG6)

The logical output signal operation function allows you to make
the inverter internally perform a logical operation of output
signals.
This function applies to all output signals, except to logical
operation results (LOG1 to LOG6).
Three types of operators (AND, OR, and XOR) are selectable.
Output signal 1
Output signal 2
LOGx (AND)
LOGx (OR)
LOGx (XOR)
The necessary parameters depend on the logical output signal to be operated. The following table lists the
parameters to be set for each logical output signal:
Selected signal
33: Logical output signal 1 (LOG1)
34: Logical output signal 2 (LOG2)
35: Logical output signal 3 (LOG3)
36: Logical output signal 4 (LOG4)
37: Logical output signal 5 (LOG5)
38: Logical output signal 6 (LOG6)
(Example) To output the AND of the running signal (00: RUN) and set the frequency overreached signal
(02: FA2) as the logical output signal 1 (LOG1) to the intelligent output terminal [2]:
- Intelligent output terminal [2] (C002): 33 (LOG1)
- Logical output signal 1 selection 1 (C142): 00 (RUN)
- Logical output signal 1 selection 2 (C143): 02 (FA2)
- Logical output signal 1 operator (C143): 00 (AND)
When "4 bits" is selected
Factor code
Cause of tripping
Temperature error due to
E20, E21
low cooling-fan speed
Temperature error
E24
Phase loss input protection
Easy sequence user trip 0-9,
E50 to E79
option 1,2 error 0-9
Function code
C062
Operation-target 1
selection
Factor code
Data
00
01
02
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C142: Logical output signal 1 selection 1
C143: Logical output signal 1 selection 2
C144: Logical output signal 1 operator selection
C145: Logical output signal 2 selection 1
C146: Logical output signal 2 selection 2
C147: Logical output signal 2 operator selection
C148: Logical output signal 3 selection 1
C149: Logical output signal 3 selection 2
C150: Logical output signal 3 operator selection
C151: Logical output signal 4 selection 1
C152: Logical output signal 4 selection 2
C153: Logical output signal 4 operator selection
C154: Logical output signal 5 selection 1
C155: Logical output signal 5 selection 2
C156: Logical output signal 5 operator selection
C157: Logical output signal 6 selection 1
C158: Logical output signal 6 selection 2
C159: Logical output signal 6 operator selection
Operation-target 2
selection
C142
C143
C145
C146
C148
C149
C151
C152
C154
C155
C157
C158
4 - 66
When "3 bits" is selected
Cause of tripping
Description
No output of alarm code
Output of 3-bit code
Output of 4-bit code
Related code
Operator
selection
C144
C147
C150
C153
C156
C159

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents