Hitachi SJ700B Series Instruction Manual page 56

Sj700b series inverter
Hide thumbs Also See for SJ700B Series:
Table of Contents

Advertisement

- Use the
and/or
1
reverse operation, and then press the
(The display reverts to [F004].)
7) Set the monitor mode.
- To monitor the output frequency, display the function code "d001", and then press the
(The monitor shows the output frequency.)
To monitor the operation direction, display the function code "d003", and then press the
once.
(The monitor shows
8) Press the
key to start the motor.
RUN
(The RUN lamp [green LED] goes on.)
9) Press the
STOP/
key to decelerate or stop the motor.
RESET
(When the motor stops, the RUN lamp [green LED] goes off.)
-
During the test run, confirm that the inverter does not trip while accelerating or decelerating the motor
and that the motor speed and frequencies are correct.
-
If a trip due to overcurrent or overvoltage has occurred during the test run, increase the acceleration
and deceleration time.
-
Make sure that there is enough margin to trip level by monitoring the output current (d002) and DC
voltage (d102).
key to change the displayed value to "00" for forward operation or "01" for
2
key once to determine the operation direction.
STR
for forward operation,
3 - 11
Chapter 3 Operation
for reverse operation, or
key once.
FUNC
key
FUNC
for stopping.)