4.2.32 Over voltage supression during deceleration
- The over voltage supression function allows you to prevent the
inverter from tripping because of the overvoltage that can be caused by
the energy regenerated by the motor during deceleration.
- You can enable or disable the function by setting the overvoltage
suppression enable (b130).
- When "01" (enabling the over voltage supression [with deceleration stop]) is specified for the overvoltage
suppression enable (b130), the inverter will decelerate by keeping the voltage of the main circuit DC
section at over voltage suppression level (b131).
- When "02" (enabling the overvoltage suppression [with acceleration]) is specified for the overvoltage
suppression enable (b130), the inverter will start acceleration according to the acceleration and
deceleration rate at overvoltage suppression (b132) if the voltage of the main circuit DC section exceeds
the overvoltage suppression level (b131). Subsequently, the inverter will restart deceleration when the
voltage falls below the level (b131).
Item
Overvoltage suppression
enable
Overvoltage suppression
level (See Note 4.)
Acceleration rate at
overvoltage suppression
Overvoltage suppression
propotional gain
Overvoltage suppression
integral time
(Example 1) When "b130" is "01":
Voltage of the main circuit
DC section (V)
Overvoltage
suppression level
(b131)
Output frequency
(Hz)
Start of
deceleration
Note 1:When this function is enabled, the actual acceleration time may be prolonged over the set time.
Note particularly that the motor may not be decelerated if the setting of "b131" is too small when "02" is specified for the
overvoltage suppression enable (b130).
Note 2:This overcurrent restraint function does not maintain the DC voltage at a constant level. Therefore, inverter trips due to
overvoltage may be caused by the setting of the deceleration rate or by a specific load condition.
Note 3:When this function is enabled, the inverter may requires a long time to decelerate and stop the motor if the load on the motor
or the moment of inertia on the motor is under a specific condition.
Note 4:If a voltage lower than the input voltage is specified for b131, the motor cannot be stopped.
Note 5:When "01" is specified for b130, PI control is performed so that internal DC voltage is maintained at a constant level.
- Setting a higher proportional gain (b133) results in a faster response. However, an excessively high proportional gain causes control
to diverge and results in the inverter easily tripping.
- Setting a shorter integral time (b134) results in a faster response. However, an excessively short integral time results in the inverter
easily tripping.
Function code
Data or range of data
b130
330 to 390 (V)
b131
660 to 780 (V)
b132
0.10 to 30.00 (s)
b134
b135
Time (s)
Stop of
deceleration
Stop of
deceleration
Restart of
deceleration
Time (s)
Chapter 4 Explanation of Functions
00
Disable
Enabling the overvoltage suppression
01
(with controlled deceleration) (See
example 1.) (note5)
Enabling the overvoltage suppression
02
(with acceleration) (See example 2.)
Level setting for 200 V class models
Level setting for 400 V class models
Specifying the acceleration rate to be
applied when the function is enabled
Overvoltage suppression propotional gain
0 to 255
setting (valid when b130=01)
Overvoltage suppression integral time
0 to 65535
setting (valid when b130=01)
(Example 2) When "b130" is "02":
Voltage of the main circuit
DC section (V)
Overvoltage
suppression level
(b131)
Output frequency
(Hz)
deceleration
4 - 41
Related code
b130: Overvoltage suppression enable
b131: Overvoltage suppression level
b132: Acceleration and deceleration
rate at overvoltage suppression
Description
Start of
Acceleration according to
the setting of "b132"
Time (s)
Time (s)