(x) 09 command: This command checks whether set data can be stored in the EEPROM in the inverter.
- Transmission frame
Frame format
STX
Station No. Command
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
BCC
Block check code
CR
Control code (Carriage Return)
- Response frame
Frame format
STX
Station No.
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
ACK
Control code (acknowledgement)
Data
Data
BCC
Block check code
CR
Control code (Carriage Return)
Negative response: See Item (4)-(ii) of this section.
(xi) 0A command: This command stores set data in the EEPROM in the inverter.
- Transmission frame
Frame format
STX
Station No. Command
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
BCC
Block check code
CR
Control code (Carriage Return)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.
BCC
Description
ACK
Data
Description
BCC
Description
Chapter 4 Explanation of Functions
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
2 bytes
09
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
BCC
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
1 byte
ACK (0x06)
2 bytes
"01" (enabling data storage)
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
2 bytes
0A
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
4 - 125
Setting
Setting
Setting

Hide quick links: