A. ......... *12" (30cm) minimum: clearance above grade, veranda, porch, deck, or balcony.
B. ......... *12" (30cm) minimum: Clearance to window or door that may be opened.
C. ......... 12" (30cm) minimum: Clearance to permanently closed window (recommended to prevent condensation on
window.
D. ......... 18" (46cm) minimum: Vertical clearance to ventilated soffit located above the terminal within a horizontal
distance of 2' (60cm) from the centerline of the terminal.
E. ......... 12" (30)cm) minimum: Clearance to unventilated soffit.
F. ......... 6" (15cm): Clearance to outside corner.
G. ......... 9" (23cm): Clearance to inside corner.
............. *Not to be installed above a meter/regulator (gas or electrical) assembly within 3' (90cm) horizontally from
the centerline of the meter/regulator.
H. ......... *6' (1.8m) minimum: Clearance to service regulator vent outlet.
I. .......... *12" (30cm) minimum: Clearance to nonmechanical air supply inlet to building or the combustion air inlet
to any other appliance.
J. .......... *6' (1.8m) minimum: Clearance to a mechanical air supply air inlet.
K. ......... *+7' (2.1m) minimum: Clearance above paved sidewalk or a paved driveway located on public property.
L........... *#12" (30 cm) minimum: Clearance under veranda, porch, deck, or balcony.
M.......... 6" (15 cm) minimum: Clearance to adjacent building or deck.
N. ......... 6" (15 cm) minimum: Clearance to nearby building
+A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single-family
dwellings and serves both dwellings.*
#Only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of two sides beneath the floor.*
*As specified in CGA B149 Installation Codes
Note: Local Codes or regulations may require different clearances.
D
N
B
L
= vent terminal
V
03/21/01 #250-6120
QFP 30 Direct Vent Gas Fireplace
HORIZONTAL TERMINATION REQUIREMENTS
E
Openable
V
B
F
K
A
= air supply inlet
A
V
H
Fixed
Closed
C
I
V
A
A
= area where terminal is not permitted
M
G
V
J