Vent Information; Venting Termination Minimum Requirements - Quadra-Fire Santa Fe Pellet Insert Installation Manual

Table of Contents

Advertisement

4

Vent Information

A. Venting Termination Minimum Requirements
O
Figure 13.1
All minimum clearances are listed with an Outside Air Kit (OAK) installed, unless otherwise noted in table below.
A
12 in.
Above Finish Grade (the grade surface
must be a non-combustible material
B
12 in.
Open door or window: below or to the side
48 in. no OAK
B
12 in.
Open door or window: above
C
6 in.
Permanently closed window: above, below
or to the side
D
18 in.
Vertical clearance to a ventilated soffit
36 in. no OAK
located above the terminal within a hori-
zontal distance of 2 ft from the center-line
of the terminal
E
12 in.
Clearance to unventilated soffit
F
12 in.
Clearance to outside corner
G
12 in.
Clearance to inside corner
H
36 in.
Above gas meter/regulator measured from
horizontal center-line of regulator
I
36 in. USA
Clearance to service regulator vent outlet
72 in. Canada
J
12 in.
Clearance to non-mechanical air supply
48 in. no OAK
inlet to the building or the combustions air
inlet to any other appliance
K
10 ft horizontal
Clearance to mechanical air supply
3 ft vertical
L
7 ft.
Above paved sidewalk, paved driveway
located on public property
M
12 in.
Under an open veranda, porch, deck or
balcony
N
See Note
Electric service: above, below or to the
below*
side (location must not obstruct or interfere
with access)
O
24 in.
Adjacent building, fences and protruding
parts of the structure
P
12 in.
Clearance above roof line for vertical
terminations
*NOTE: Consult local building, fire officials or authorities
having jurisdiction. Local codes or regulations may
require different clearances.
October 23, 2018
D
E
L
C
B
V
FIXED
CLOSED
OPEN
F
V
B
Termination Cap
V
Inside Corner
G
V
A
FIXED
OPEN
V
CLOSED
B
V
A
B
G
Air Supply Inlet
Gas Meter
X
24 in.
Above grass, top of plants, wood or any other com-
bustible
12 in.
Clearance from any forced air intake of other appli-
36 in. no OAK
ance
12 in.
Clearance horizontally from combustible wall
15 in.
Vented directly through a wall, minimum length of
horizontal pipe
6 in. horizontal
Minimum horizontal or vertical terminations must
12 in. vertical
protrude from wall
Do NOT Terminate Vent:
In any location that will allow flue gases or soot from
entering or staining the building
In any location which could create a nuisance or
hazard
In any enclosed or semi-enclosed area such as a
carport, garage, attic, crawl space, under a sun deck
or porch, narrow walkway
Closely fenced area, or any location that can build up
a concentration of fumes such as a stairwell, covered
breezeway, etc.
Termination must exhaust above air inlet elevation.
It is recommended that at least 60 inches (1.52m) of
vertical pipe be installed when appliance is vented
directly through a wall. This will create a natural draft,
which will help prevent the possibility of smoke or
odor venting into the home during a power outage.
It will also keep exhaust from causing a nuisance
or hazard by exposing people or shrubs to high
temperatures.
The safest and preferred venting method is to extend
the vent vertically through the roof or above the roof.
7019-230J
SANTA FE PELLET INSERT
V
N
N
N
Electrical
V
V
Service
N
V
H
P
G
M
I
X
V
J or K
Restricted Area
NOTICE
NOTICE
13

Advertisement

Table of Contents
loading

Table of Contents