CLIMATIC 50 – ROOFTOP – VERSION 23
SCHEDULING – CLOCK SETTING
Scheduling
Function
Controlling operation of the unit according to the time and day
Description
CLIMATICTM 50 can handle 4 time zones over the 7 days of the week:
Zone unoccupied
Zone A
Zone B
Zone C
Each set point integrates the hour and minute's adjustment, thus a value of 8.3 equal 8.30 a.m.
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
For each time zone, the set following set points following can be modified:
Note: "Monday" is considered as the first day of the week for programming the CLIMATIC™50.
Factory settings:
BALTIC R410A-IOM-0708-E
8h00
Unoccupied
Z :A
LIST SET POINT BY ZONE
Ambient temperature
Minimum fresh air (%)
Beginning of zone; each day
"Day A" activated from Monday to Saturday 6h22h
Night mode (unoccupied) for the remaining of time, Sunday included
(Night)
(Day A)
(Day B)
(Day C)
12h00
13h50
Z :B
Set point average
Set point dynamic
Programming
Start Uno
Start z.A
Start z.B
Start z.C
20h30
22h00
Z :C
Unoccupied