VENTILATION: FANSTART
AIR SOCK CONTROL
Menu
Press the Button "Mode" to enter and exit menus
-
-
The Vertical arrows allow to seek each options
The "Enter" button allow to select a menu or a parameter to modify it, it also allows to validate it once
-
modified
Quick Setting
Press the mode button and enter the quick menu "AUF"
-
Modify and check the "AUF" sub-menus
-
AU1 "automatic acceleration/deceleration" must be set to ZERO
o
Acc "acceleration" : set to 50 s
o
Dec "deceleration" : set to 30 s
o
LL "low speed" : set to 0Hz
o
UL "high spee" : set to 50Hz
o
tHr "motor thermal current" : adjust this setpoint equal to nominal motor amps
o
uL " motor nominal frequency" : set to 50Hz
o
uLu "nominal motor voltage" : set to 400V
o
If those parameters are unseen, check that the "loc rem" button located in front is lighting because this allows a
remote parameter control. Push this button to get the control back into the display
BALTIC R410A-IOM-0708-E