HEATING: GAS BURNER
BURNER SAFETY CHECKS
Smoke extractor pressure switch Test.
With the gas burner running, disconnect the flexible tube
fitted to the pressure taping on the pressure switch (Fig.
57).
The Flame must disappear and the extraction fan must
carry on running.
However, NO fault will be displayed (Gas ignition control
block or CLIMATIC).
Fig. 57
After reconnecting of the tube, the Burner will restart
after a period of 30 to 45 seconds pre-ventilation.
Gas pressure switch test
With the gas burner running, close the shut off valve
located before the rooftop. (fig. 58)
Fig. 58
The burner stops completely.
However, No fault light will be displayed on the Gas
ignition control block. After 6 Minutes, the CLIMATIC will
display a fault.
Reset the CLIMATIC.
BALTIC R410A-IOM-0708-E
Ionisation Probe test
With the gas burner running, disconnect the terminal plug
coming from the ionisation probe to the gas ignition
control box.
Fig. 59
The flame disappears
The fan is still running and attempting to restart the
burner (restart cycle 30 to 45 seconds).
if the ignition probe is not reconnected at the end of the
ignition sequence the burner will stop completely.
The fault light on the gas ignition control block is ON.
Manually reset the gas ignition control block to eliminate
the fault
IN CASE OF PROBLEMS REFER TO THE START UP
SEQUENCE FLOWCHART NEXT PAGE