CLIMATIC 50 – ROOFTOP – VERSION 23

LonWorks

In
de
Type
x
Name NV
pC
O
ANL
1 I_Sp_T_Cool_BMS
ANL
1 O_Sp_T_Cool_BMS
ANL
2 I_Sp_T_Heat_BMS
ANL
2 O_Sp_T_Heat_BMS
ANL
3 I_Sp_T_Cool_Uno
ANL
3 O_Sp_T_Cool_Uno
ANL
4 I_Sp_T_Heat_Uno
ANL
4 O_Sp_T_Heat_Uno
ANL
5 I_Sp_Hr_Dehu_BMS
ANL
5 O_Sp_Hr_Dehu_BMS
ANL
6 I_Sp_Hr_Humi_BMS
ANL
6 O_Sp_Hr_Humi_BMS
ANL
17 O_T_Room
ANL
18 O_T_Outside
ANL
19 O_Ia_T_Supply
ANL
20 O_Hr_Room
ANL
21 O_Ha_Room
ANL
22 O_Hr_Outside
ANL
23 O_Ha_Outside
INT
1 I_Sp_BMS_Dog
INT
1 O_Sp_BMS_Dog
INT
2 I_Sp_EcoMini_BMS
INT
2 O_Sp_EcoMini_BMS
INT
3 I_Hour
INT
3 O_Hour
INT
4 I_Minute
INT
4 O_Minute
INT
5 I_Day
INT
5 O_Day
INT
6 I_Month
INT
6 O_Month
INT
17 O_Error_Codes
INT
18 O_Oa_Eco
INT
19 O_Oa_GasHeat
INT
20 O_Oa_TriacHeat
INT
21 O_Oa_HotWater
DGT
1 I_Sp_On_Unit
DGT
1 O_Sp_On_Unit
DGT
2 I_Sp_Reset
DGT
2 O_Sp_Reset
DGT
3 I_Sp_Unoc
DGT
3 O_Sp_Unoc
DGT
4 I_Clock
DGT
17 O_Od_Alarm
BALTIC R410A-IOM-0708-E
Index
Type NV
Direction
pCO
105 input
105 output
105 input
105 output
105 input
105 output
105 input
105 output
81 input
81 output
81 input
81 output
105 output
105 output
105 output
81 output
23 output
81 output
23 output
8 input
208
8 output
208
8 input
209
8 output
209
8 input
210
8 output
210
8 input
211
8 output
211
8 input
212
8 output
212
8 input
213
8 output
213
8 output
224
81 output
225
81 output
226
81 output
227
81 output
228
95 input
415
95 output
415
95 input
416
95 output
416
95 input
417
95 output
417
95 input
418
95 output
431
1
[Occupation][Room SP] Required maximum
room temperature in °C. Cooling set point
1
2
[Occupation][Room SP] Required minimum
room temperature in °C. Heating set point
2
3
[Unoccupied][Room SP] Required maximum
room temperature in °C. Cooling set point
3
4
[Unoccupied][Room SP] Required minimum
room temperature in °C. Heating set point
4
5
[Humidity] Desired Maximum relative humidity
in Room (in %). – Dehumidification set point.
5
6
[Humidity] Desired Minimum relative humidity
in Room (in %). – Humidification set point.
6
17
[Temperature] Room
18
[Temperature] Outdoor
19
[Temperature] Supply
20
[Relative Humidity] Room
21
[Absolute Humidity] Room
22
[Relative Humidity] Outdoor
23
[Absolute Humidity] Outdoor
[ BMS ] Activation of the control by a computer
or an automat - mode BMS is activated if this
value is different from zero, This value is
decreased every second
[Room SP] Required room minimum fresh air
rate in % Middle of the dead zone.
[Clock] Hour
[Clock] Minute
[Clock] Day of the month
[Clock] Month
[Alarm] Code Error
[% of opening] Damper of fresh air
[% of opening] Valve gas
[% of opening] Electrical heaters (Triac)
[% of opening] Hot water coil
[On / Off] Unit
[Reset] Discharges the safety measures of the
unit
[BMS] Activation of the Unoccupied mode [Off]
Occupied mode - [On] Unoccupied mode
[Clock] [OFF] read hour & minute [ON] write
hour & minute
[Alarm] General
DS50
3322
(BMS)
3323
(BMS)
3322
(Uno)
3323
(Uno)
3341
(BMS)
3342
(BMS)
2112
2111
2113
2122
2124
2121
2123
3932
3312
(BMS)
3121
3122
3123
3124
1000
2413
2618
2627
2633
3111
3112
3933
...
1000