Analog Inputs; Ambient Temperature Setpoint Offset - 4-20 Ma Signal; Minimum Fresh Air Setpoint - 4-20Ma Signal; Entry For A Meteorological Sensor - Lennox BAC020SNM Installation, Operating And Maintenance

Table of Contents

Advertisement

CLIMATIC 50 – ROOFTOP – VERSION 23

Analog Inputs

The following items can be used for each input:
[Not Used] .......................... Not used
[S.P Offset]......................... Room temperature set point offset – 4-20mA signal.
[F.A Offset]......................... Minimum fresh air set point – 4-20mA signal.
[Weather T.] ....................... Entry for a Meteorological temperature sensor
[Weather H.] ....................... Entry for a Meteorological humidity sensor
[Free NTC] ......................... Free temperature probe connection
[Free Hr.]............................ Free relative humidity sensor connection
Ambient Temperature Set Point Offset – 4-20mA Signal:
The 4-20mA signal sent to the unit is linearly converted using a -5K to +5K range of temperature set point.
For example: for a unit set point of 20°C
A 4mA signal will give a 15°C unit temperature set point
A 12mA signal will give a 20°C unit temperature set point
A 20mA signal will give a 25°C unit temperature set point
Minimum Fresh Air Set Point – 4-20mA Signal:
The 4-20mA signal sent to the unit is linearly converted to a 0% - 100% fresh air damper opening request.
Entry for a Meteorological Temperature Sensor:
The 4-20mA signal sent to the unit is linearly converted using a -40°C to +80°C range, this measure will replace the one
given by the unit sensor.
Input for a Meteorological Sensor for Relative Humidity:
The 4-20mA signal sent to the unit is linearly converted using a 0% to 100% range, this measure will replace the one given
by the unit sensor.

Free Temperature Probe Connection:

Lennox NTC sensor.

Free Relative Humidity Sensor Connection:

The 4-20mA signal sent to the unit is linearly converted using a 0% to 100% range.
BALTIC R410A-IOM-0708-E
4/20mA Signal
-
+
NTC
Probe
Example BE50-
J9.B1,
BE50-J9.B2
Page 99