Lennox LGA Series Unit Information
Hide thumbs Also See for LGA Series:

Advertisement

Service Literature
The LGA /LGC/ LCA/LCC 21, 25 and 30 ton (74, 88, 105 kW)
units are configured to order units (CTO) with a wide selection
of factory installed options. The LGA/LGC248H/360H gas/
electric packaged rooftop units are available in 260,000 Btuh,
360,000 Btuh and 480,000 Btuh (76.2 kW, 105.5 and 137.7
kW) heating inputs. Gas heat sections are designed with Len-
nox' aluminized steel tube heat exchangers. The LCA/
LCC248H/360H cooling packaged rooftop units are
equipped with the same cooling sections as the LGA/
LGC248H/360H units.
LCA/LGA248, LCC/LGC300H and LCC/LGC360H units
may contain a supply air blower equipped with a variable
frequency drive A96 (VFD) which varies supply air CFM. As
duct static increases, the supply air volume will decrease.
As duct static decreases, the supply air volume will in-
crease.
Optional electric heat is factory−or field−installed in LCA /LCC
units. Electric heat operates in single or multiple stages de-
pending on the kW input size. 30kW through 120kW heat
sections are available for the LCA/LCC248H/360H. LGA/
LGC and LCA/LCC units have identical refrigerant circuits
with 21, 25 and 30 ton (74, 88 and 105kW) cooling capaci-
ties. LGA/LCA360H units utilize three compressors, while
the LGA/LCA300H and LGA/LCA248H units utilize four
compressors.
Units are also designed for R−410A refrigerant. See unit
nameplate for refrigerant type and charge. Operating pres-
sures and pressure switch settings are significantly higher
than units charged with R−22. Service equipment for
R−410A units must be rated for R−410A refrigerant.
The LGA and LCA units are designed to accept any of sev-
eral different energy management thermostat control sys-
tems with minimum field wiring. Factory or field provided
control options connect to the unit with jack plugs. When
"plugged in" the controls become an integral part of the unit
wiring.
Information contained in this manual is intended for use by
qulified service technicians only. All specifications are sub-
ject to change. Procedures outlined in this manual are pre-
sented as a recommendation only and do not supersede or
replace local or state codes.
Corp. 9913−L7
Revised 01−2009
LGA/LGC/LCA/LCC SERIES
If the unit must be lifted for service, rig unit by attaching four
cables to the holes located in the unit base rail (two holes at
each corner). Refer to the installation instructions for the prop-
er rigging technique.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.
Page 1
LGA/LGC
LCA/LCC
LGA360
WARNING
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon-
nect switch(es). Unit may have multiple
power supplies.
© 1999 Lennox Industries Inc.
21 / 30 TON
74 / 105 kW
Litho U.S.A.

Advertisement

Table of Contents
loading

Summary of Contents for Lennox LGA Series

  • Page 1: Introduction

    Procedures outlined in this manual are pre- electrical power to unit OFF at discon- nect switch(es). Unit may have multiple sented as a recommendation only and do not supersede or power supplies. replace local or state codes. © 1999 Lennox Industries Inc. Page 1 Litho U.S.A.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Introduction ......Page 1 V−MAINTENANCE ..... . . Page 59 Specifications .
  • Page 3: Specifications

    SPECIFICATIONS LGA/LCA General Nominal Tonnage (kW) 21 Ton 21 Ton 21 Ton 21 Ton Data Model No. 248H2B 248H4B 248H2V 248H4V Efficiency Type High High High High Blower Type Constant Air Constant Air Variable Air Variable Air Volume (CAV) Volume (CAV) Volume (VAV) Volume (VAV) Cooling...
  • Page 4 SPECIFICATIONS LGA/LCA General Nominal Tonnage (kW) 25 Ton 25 Ton 25 Ton 25 Ton Data Model No. 300H2B 300H4B 300H2V 300H4V Efficiency Type High High High High Blower Type Constant Air Constant Air Variable Air Variable Air Volume (CAV) Volume (CAV) Volume (VAV) Volume (VAV) Cooling...
  • Page 5 SPECIFICATIONS LGC/LCC General Nominal Tonnage (kW) 30 Ton Data Model No. 360H2B 360H4B 360H2V 360H4V Efficiency Type High High High High Blower Type Constant Air Constant Air Variable Air Variable Air Volume (CAV) Volume (CAV) Volume (VAV) Volume (VAV) Cooling Gross Cooling Capacity −...
  • Page 6 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
  • Page 7: Electrical Data

    SPECIFICATIONS GAS HEAT Gas Heating Heat Input Type Standard (2 Stage) Medium (2 Stage) High (2 Stage) Performance Input − Btuh (KW) First Stage 169,000 (49.5) 234,000 (68.6) 312,000 (91.4) Second Stage 260,000 (76.2) 360,000 (105.5) 480,000 (140.6) Output − Btuh (kW) First Stage −...
  • Page 8 ELECTRICAL/ELECTRIC HEAT DATA LGA/LCA 21 TON HIGH EFFICIENCY (R−22) 248H2 Voltage − 60hz − 3 phase 208/230V 460V 575V Compressors Rated Load Amps (total) 17.3 (69.2) 9 (36) 7.1 (28.4) Locked Rotor Amps (total) 123 (492) 62 (248) 50 (200) Outdoor Fan Full Load Amps (total) 2.4 (14.4)
  • Page 9 ELECTRICAL/ELECTRIC HEAT DATA LGA/LCA 21 TON HIGH EFFICIENCY (R−22) 248H2 Voltage − 60hz − 3 phase 208/230V 460V 575V Indoor Blower Motor Horsepower Electric Heat Control Kit 15K13 15K92 15K93 Disconnect with Standard 0 kW 84M14 84M14 84M14 84M13 84M13 84M13 84M13 84M13...
  • Page 10 ELECTRICAL/ELECTRIC HEAT DATA LGA/LCA 21 TON HIGH EFFICIENCY (R−410A) 248H4 Voltage − 60hz − 3 phase 208/230V 460V 575V Compressors Rated Load Amps (total) 18.1 (72.4) 9 (36) 6.8 (27.2) Locked Rotor Amps (total) 137 (548) 62 (248) 50 (200) Outdoor Fan Full Load Amps (total) 2.4 (14.4)
  • Page 11 ELECTRICAL/ELECTRIC HEAT DATA LGA/LCA 21 TON HIGH EFFICIENCY (R−410A) 248H4 Voltage − 60hz − 3 phase 208/230V 460V 575V Indoor Blower Motor Horsepower Electric Heat Control Kit 15K13 15K92 15K93 Disconnect with Standard 0 kW 84M14 84M14 84M14 84M13 84M13 84M13 84M13 84M13...
  • Page 12 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 25 TON HIGH EFFICIENCY (R−22) 300H2 Voltage − 60hz − 3 phase 208/230V 460V 575V Compressors Rated Load Amps (total) 18.6 (74.4) 9 (36) 7.4 (29.6) Locked Rotor Amps (total) 156 (624) 75 (300) 54 (216) Outdoor Fan Full Load Amps (total) 2.4 (14.4)
  • Page 13 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 25 TON HIGH EFFICIENCY (R−22) 300H2 Voltage − 60hz − 3 phase 208/230V 460V 575V Indoor Blower Motor Horsepower Electric Heat Control Kit 15K13 15K92 15K93 Disconnect with Standard 0 kW 84M14 84M14 84M14 84M13 84M13 84M13 84M13 84M13...
  • Page 14 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 25 TON HIGH EFFICIENCY (R−410A) 300H4 Voltage − 60hz − 3 phase 208/230V 460V 575V Compressors Rated Load Amps (total) 22.4 (89.6) 10.6 (42.4) 7.7 (30.8) Locked Rotor Amps (total) 149 (596) 75 (300) 54 (216) Outdoor Fan Full Load Amps (total) 2.4 (14.4)
  • Page 15 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 25 TON HIGH EFFICIENCY (R−410A) 300H4 Voltage − 60hz − 3 phase 208/230V 460V 575V Indoor Blower Motor Horsepower Electric Heat Control Kit 15K13 15K92 15K93 Disconnect with Standard 0 kW 84M14 84M15 84M15 84M13 84M13 84M13 84M13 84M13...
  • Page 16 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 30 TON HIGH EFFICIENCY (R−22) 360H2 Voltage − 60hz − 3 phase 208/230V 460V 575V Compressors Rated Load Amps (total) 22.4 (89.6) 10.9 (43.6) 8.3 (33.2) Locked Rotor Amps (total) 164 (656) 100 (400) 78 (312) Outdoor Fan Full Load Amps (total) 2.4 (14.4)
  • Page 17 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 30 TON HIGH EFFICIENCY (R−22) 360H2 Voltage − 60hz − 3 phase 208/230V 460V 575V Indoor Blower Motor Horsepower Electric Heat Control Kit 15K13 15K92 15K93 Disconnect with Standard 0 kW 84M14 84M15 84M15 84M13 84M13 84M13 84M13 84M13...
  • Page 18 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 30 TON HIGH EFFICIENCY (R−410A) 360H4 Voltage − 60hz − 3 phase 208/230V 460V 575V Compressors Rated Load Amps (total) 25 (100) 12.2 (48.8) 9 (36) Locked Rotor Amps (total) 164 (656) 100 (400) 78 (312) Outdoor Fan Full Load Amps (total) 2.4 (14.4)
  • Page 19 ELECTRICAL/ELECTRIC HEAT DATA LGC/LCC 30 TON HIGH EFFICIENCY (R−410A) 360H4 Voltage − 60hz − 3 phase 208/230V 460V 575V Indoor Blower Motor Horsepower Electric Heat Control Kit 15K13 15K92 15K93 Disconnect with Standard 0 kW 84M15 84M15 84M15 84M13 84M14 84M14 84M13 84M13...
  • Page 20: Options/Accessories

    OPTIONS/ACCESSORIES Item COOLING SYSTEM Condensate Drain Trap PVC − LTACDKP09/36 Copper − LTACDKC09/36 Corrosion Protection Efficiency High Refrigerant Type R−22 R−410A Service Valves Stainless Steel Condensate Drain Pan HEATING SYSTEM Combustion Air Intake Extensions LTACAIK10/15 Gas Heat Input Standard − 260 kBtuh input Medium −...
  • Page 21 OPTIONS/ACCESSORIES Item ELECTRICAL Voltage 208/230V − 3 phase 60 hz 460V − 3 phase 575V − 3 phase HACR Circuit Breakers Disconnect Switch See Electrical / Electric Heat Tables for selection GFI Service Outlets LTAGFIK10/15 ELECTRIC HEAT ACCESSORIES/OPTIONS − See Electrical / Electric Heat Tables for selection LTB2 Terminal Block Electric Heat Control Module Unit Fuse Block...
  • Page 22 OPTIONS/ACCESSORIES Item ROOF CURBS − CLIPLOCK 1000 Down−Flow 14 in. (356 mm) height LARMF30/36S−14 18 in. (457 mm) height LARMF30/36S−18 24 in. (610 mm) height LARMF30/36S−24 Horizontal 30 in. (762 mm) height LARMFH30/36S−30 41 in. (1041 mm) height LARMFH30/36S−41 ROOF CURBS − STANDARD Down−Flow 14 in.
  • Page 23: Electric Heat Accessories

    OPTIONAL ELECTRIC HEAT ACCESSORIES ELECTRIC HEAT CONTROL MODULE AND UNIT FUSE BLOCKS Unit Model No. 156H 180S 180H 180H 210S 210H 240S 240H 240H 300S 248H 248H 300H 360H 360H R−22 R−410A R−22 R−410A R−22 R−410A R−22 R−410A Electric Electric Heat Model No. EHA (see Electric Heat Data tables for additional information) Heat kW Input Range...
  • Page 24: Blower / Acc. Air Resistance Data

    BLOWER DATA−BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE. FOR ALL UNITS ADD: 1 − Wet indoor coil air resistance of selected unit. 2 − Any factory installed options air resistance (heat section, economizer, etc.) 3 −...
  • Page 25 BLOWER DATA CAV FACTORY INSTALLED DRIVE KIT SPECIFICATIONS Motor RPM Range Drive 1 Drive 2 Drive 3 Drive 4 Drive 5 Drive 6 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz...
  • Page 26 BLOWER DATA BLOWER DATA Gas Heat Exchanger Wet Indoor Horizontal MERV 11 Economizer Standard Volume Coil Roof Curb Filter Medium Heat High Heat Heat w.g. w.g. w.g. w.g. w.g. w.g. w.g. 6000 2830 6500 3070 7000 3305 7500 3540 8000 3775 8500 4010...
  • Page 27 BLOWER DATA CEILING DIFFUSER AIR RESISTANCE Flush Diffuser − Step-Down Diffuser − LARTD30/36 LAFD30/36 Air Volume 2 Ends Open 1 Side/2 Ends Open All Ends & Sides Open in. w.g. in. w.g. in. w.g. in. w.g. 7500 3540 8000 3775 8500 4010 9000...
  • Page 28 BLOWER DATA POWER EXHAUST FANS − 50% HIGH STATIC OPERATION BOLD INDICATES FIELD FURNISHED DRIVE Return Duct Negative Static Pressure − Inches Water Gauge (Pa) 0 (0) .10 (25) .20 (50) .30 (75) .40 (100) .50 (125) .60 (150) .70 (175) .80 (200) .90 (225) 1.0 (250)
  • Page 29: Parts Arrangement

    LGA/LGC PARTS ARRANGEMENT EVAPORATOR FILTERS COIL (12 20 X 20 X 2 in. CONDENSER FANS [508 X 508X 51mm]) ECONOMIZER DAMPERS (OPTIONAL) BLOWERS CONTROL BOX HEAT COMPRESSORS EXCHANGER TUBES BURNERS COMBUSTION AIR BLOWER FIGURE 1 EVAPORATOR LCA/LCC PARTS ARRANGEMENT CONDENSER FANS COIL FILTERS (12 20 X 20 X 2 in.
  • Page 30 LGA/LGC/LCA/LCC CONTROL BOX ELECTRIC HEAT 2 CONTROL MODULE E1 (A60) GAS HEAT CONTROL MODULE (A58) (USED ONLY ON 45kW & HIGHER) (LGA ONLY) C.A.B TRANSFORMER and RELAYS ECONOMIZER CONTROL LGA UNITS (T3 and T13) (K13 and K19) MODULE EM1 (A56) ELECTRIC HEAT CONTROL OUTDOOR FAN RELAY...
  • Page 31: I−Unit Components

    I−UNIT COMPONENTS 3−Contactor Transformer T18 T18 is a single line voltage to 24VAC transformer used in ELECTROSTATIC DISCHARGE (ESD) all units. Transformer T18 is protected by a 3.5 amp circuit Precautions and Procedures breaker (CB18). T18 is identical to transformer T1. The CAUTION transformer supplies 24VAC power to the contactors.
  • Page 32 10−Blower Contactor K3 (all units) 14−Burner Controls A3 & A12 (LGA units) Blower contactor K3, used in all units, is a three-pole-double- All LGA and LGC units have two burner controls. A3 controls break contactor with a 24VAC coil used to energize the indoor gas heat section one, while A12 controls gas heat section two.
  • Page 33 LINE VOLTAGE IN TELEMECANIQUE OVERLOAD RELAY TRIP CLEAR INDICATON COVER WINDOW DETAIL SHOWING RESET BUTTON (SHOWN ADJUSTED TO MANUAL POSITION CLOSED) AMP SETTING Lift clear cover and turn adjustment STOP POINTER screw counterclockwise. Reset screw will BUTTON pop out when pointer is in M (manual (RED) position).
  • Page 34 ELECTRIC HEAT CONTROL SECTION 20−Compressor 2 Control Module A57 (all units) (45 − 120 kW electric heat only) The compressor 2 control module A57 controls one addi- 17−Electric Heat Relay K9 tional compressor stage for the LGA/LGC/LCA/LCC units. All LCA/LCC series units with 45 − 120 kW electric heat use an A57 includes all inputs and outputs required for compressor electric heat relay K9.
  • Page 35 IMC BOARD INPUTS AND OUTPUTS SENSORS INPUTS P114 P117 P115 P116 P120 P111 P113 P110 P112 OUTPUTS COMPRESSOR SAFETY INPUTS BURNER ROOM INPUTS THERMOSTAT (A2) TB1 connects to P110. Room thermostat connects to TB1. See section C2 in the wiring diagram section P.65 IMC AND ADD−ON BOARD LOCATION AND OPERATION 1 Blower 1 Gas valve...
  • Page 36 CAV REFRIGERANT CIRCUITS EVAPORATOR COIL STAGE 2 EVAPORATOR COIL STAGE 1 EVAPORATOR COIL STAGE 1 CONDENSER COIL STAGE 2 CONDENSER COIL FIGURE 8 VAV UNIT REFRIGERANT CIRCUITS CIRCUIT 4 CIRCUIT 3 STAGE 2 EVAPORATOR COIL STAGE 1 STAGE 1 EVAPORATOR CONDENSER COIL COIL STAGE 2...
  • Page 37 360H PLUMBING COMPONENTS FREEZESTATS (3) ONE FOR EACH STAGE OF 3 compressors COIL (LOCATED ON LIQUID LINE RETURN BENDS) LOW AMBIENT SWITCHES SUCTION (S11) (S84) (S85) LINE (3) LOW PRESSURE SWITCHES (S87) (S88) (S98) DRIERS (B1) STG. 1 SERVICE (B2) STG.
  • Page 38 248H, 300H, 360H PLUMBING COMPONENTS FREEZESTATS (4) ONE FOR EACH STAGE OF COIL (LOCATED ON LIQUID LINE (4) THE RETURN BEND) LOW AMBIENT SWITCHES SUCTION LINE (4) (S11) (S84) (S85) (S94) (S7) (S88) CIRCUIT 2 (S28) (S98) (STG 1) DRIER (4) CIRCUIT 3 (STG 2) (S96) (S97)
  • Page 39: Cooling Components

    B−Cooling Components Figures 10 and 11 IMPORTANT All units use independent cooling circuits (figures 8 and 9) Pressure switch settings are significant higher on consisting of separate compressors, condenser coils and R410A charged units than R22 charged units. evaporator coils. Six draw−through type condenser fans are used in all units.
  • Page 40: Blower Compartment

    Units charged with R22 6−Service Valve (optional all units) When liquid pressure rises to 275 +10 psig (1896 + 69 Units may be equipped with service valves located in the kPa), the switch closes and the condenser fan is ener- discharge and liquid lines.
  • Page 41 1−Blower Wheels (all units) C−Determining Unit CFM All units have two 18 in. x 15 in. (457 mm x 381 mm) blower 1− The following measurements must be made with a dry wheels. Both wheels are driven by one motor. indoor coil.
  • Page 42 BLOWER ASSEMBLY BELT TENSION TO INCREASE CFM LOOSEN SCREWS TO ADJUSTING SCREWS LOOSEN ALLEN SCREW & ADJUST BELT TENSION ALLEN TURN PULLEY CLOCKWISE SCREW TO DECREASE CFM LOOSEN SCREWS TURN PULLEY SIDE VIEW TO ADJUST BELT COUNTERCLOCKWISE TENSION BLOWER MOTOR MOTOR ALLEN SCREW...
  • Page 43 HEAT EXCHANGER TUBE COMBUSTION AIR INDUCER (B15) VENT CONNECTOR GAS VALVE (GV3) BURNER FIGURE 15 COMBUSTION HEAT EXCHANGER TUBE AIR INDUCER FLAME ROLLOUT LIMIT S69 VALVE BURNERS FIGURE 16 Page 43...
  • Page 44: Gas Heat Components

    D−GAS HEAT COMPONENTS (all LGA units) units. Loss of flame during a heating cycle is indicated by an absence of flame signal (0 microamps). If this happens, the LGA300/360 production units to July 2004 are available control will immediately restart the ignition sequence and then in 260,000 BTUH (76.2 kW) standard gas heat or lock out if ignition is not gained after the third trial.
  • Page 45 É É É NORMAL IGNITION SEQUENCE ON / CLOSED É É É TIMINGS NOMINAL OFF / OPEN SECONDS 0 END OF DEMAND É É É É É É É É É É É É É É THERMOSTAT DEMAND COMBUSTION AIR BLOWER É...
  • Page 46 SPDT N.C. auto−reset limits. Each orifice and burner are sized specifically to the unit. Refer to Lennox Repair Parts Listing for correct sizing in- Limit set point are factory set and cannot be adjusted. If limit formation. must be repalced, same type and set point must be used. See Lennox Repair Parts Handbook.
  • Page 47 7−Combustion Air Prove Switches S18 & S45 LGA/LGC HEATING COMPONENTS Prove switches S18 (first heat section) and S45 (second heat (Production to July 2004) section) are located in the compressor compartment. Switches SECONDARY HIGH TEMP. LIMIT S21 are identical, SPST N.O. and monitor combustion air inducer FIRST HEAT SECTION and S100 (SECOND HEAT SECTION operation.
  • Page 48 10−Gas Valves GV1 and GV3 11−Spark Electrodes An electrode assembly is used for ignition spark. Two Gas valves GV1 and GV3 are identical. The gas valves are two-stage redundant valves. Units are equipped with valves identical electrodes are used (one for each gas heat manufactured by White−Rodgers or Honeywell.
  • Page 49: Electric Heat Components

    E−Optional Electric Heat Components 3−High Temperature Limits S15 and S107 (Primary) S15 and S107 are SPST N.C. auto-reset thermostats lo- See ELECTRICAL/ELECTRIC HEAT DATA tables for pos- cated on the back panel of the electric heat section below sible LCA/LCC to EHA matchups and electrical ratings. the heating elements.
  • Page 50 TABLE 5 LCA / LCC ELECTRIC HEAT SECTION FUSE RATING FUSE (3 each) EHA QUANTITY VOLTAGES & SIZE F3 − 1 F3 − 2 F3 − 3 F3 − 4 F3 − 5 F3 − 6 F3 − 7 F3 − 8 60 Amp 60 Amp 208/230V...
  • Page 51 ELECTRIC HEAT VESTIBULE PARTS ARRANGEMENT TERMINAL STRIP FIRST HEAT SECTION (LEFT SIDE) (TB3) ACCESS DOOR FUSE F3 FIRST STAGE ELECTRIC SECOND STAGE ELECTRIC FUSE F3 FUSE F3 FUSE F3 F3 - 1 HEAT CONTACTOR K15 HEAT CONTACTOR K16 F3 - 4 F3 - 2 F3 - 3 TERMINAL STRIP...
  • Page 52: Ii−Placement And Installation

    II−PLACEMENT AND INSTALLATION B−Cooling Start−Up 1− Initiate first and second stage cooling demands ac- Make sure the unit is installed in accordance with the cording to instructions provided with thermostat. installation instructions and all applicable codes. See 2− First−stage thermostat demand will energize com- accessories section for conditions requiring use of the pressors 1 and 2.
  • Page 53: Charging

    R410A Refrigerant 6− If discharge pressure is high, remove refrigerant from the system. If discharge pressure is low, add refriger- Units charged with R410A refrigerant operate at much ant to the system. higher pressures than R22. The expansion valve and liquid line drier provided with the unit are approved for use with D Add or remove charge in increments.
  • Page 54 TABLE 9 TABLE 13 LGA/LCA Series 248 − R410A − VAV LGC/LCC Series 300H − R410A − VAV CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4 Outdoor Outdoor Coil En- Coil En- tering Air tering Air psig...
  • Page 55: Heating Start Up

    TABLE 17 TABLE 20 LGC/LCC Series 360 R410A − VAV Liquid Temp. Minus Ambient Temp. Unit CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4 1st Stage 2nd Stage 3rd Stage 4th Stage Outdoor Coil En- 248 R22 8°F+1 8°F+1 8°F+1 8°F+1 tering Air CAV/VAV...
  • Page 56: Safety Or Emergency Shutdown

    HONEYWELL VR8305Q SERIES GAS VALVE WARNING HIGH FIRE LOW FIRE ADJUSTMENT ADJUSTMENT Danger of explosion. Can cause injury or product or property damage. If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
  • Page 57: System Service Checks

    The use of specialty Gas Leak Detector is 2− While waiting for the unit to stabilize, notice the strongly recommended. It is available through Lennox flame. The flame should be stable without flashback under part number 31B2001. See CORP 8411−L10, for and should not lift from the burner heads.
  • Page 58 3− After allowing the unit to stabilize for five minutes, re- BURNER REMOVAL / SENSOR ORIENTATION cord the manifold pressure and compare to the values BURNER given for gas supply pressure in table 4. SUPPORT BURNERS CAUTION Disconnect heating demand as soon as an accurate reading has been obtained.
  • Page 59: Cooling System Service Checks

    2− Remove lead from sensing electrode and install a V−MAINTENANCE 0−50DC microamp meter in series between the sens- ing electrode and the sensing lead. CAUTION 3− Reconnect power and adjust thermostat for Electrical shock hazard. Turn off power to unit heating demand.
  • Page 60: Electrical

    A−LARMF18/36-14, 24 or LARMH30/36−30,41 Mounting Frames UNIT BASE RAIL When installing the LGA/LGC/ LCA/LCC units on a combus- tible surface for downflow discharge applications, the Lennox FIBERGLASS LARMF18/36 14-inch or 24-inch (356 mm or 610mm) height INSULATION (Furnished) roof mounting frame is used. For horizontal discharge applica-...
  • Page 61: Transitions

    Filter Handicoater when dry prior to reinstalla- tion. Filter Handicoater is R.P. Products coating no. 418 and is available as Lennox Part No. P−8−5069. E−LAREMD30/36 Economizer (Field or Factory Installed)
  • Page 62: Laged(H) Gravity Exhaust Dampers

    1− TMP" MODE (SENSIBLE TEMPERATURE) LAGED AND LAPEF In the TMP" mode, the IMC uses input from the factory INSTALLATION installed RT6 Supply Air Sensor, RT16 Return Air Sensor, and ECONOMIZER RT17 Outdoor Air Sensor to determine suitability of outside air FRESH AIR and economizer damper operation.
  • Page 63: Control Systems

    b − Thermostat switch (S60) is an auto-reset SPST K−Blower Proving Switch S52 N.C. switch which opens on a temperature rise. The blower proving switch monitors blower operation and The switch is wired in series with HR6 and T20. locks out the unit in case of blower failure. The switch is When the temperature rises above 20°F (-6.7°C) N.O.
  • Page 64: Wiring Diagrams / Operation Sequence

    The supply air VFD (A96) is located near the compressors. Supply Air VFD By−Pass Plug (Optional) See figure 39. The supply air VFD may be by−passed using jack/plug con- nections. Locate J/P198 connectors in control box area un- Excessive Duct Static der the relays.
  • Page 65: Unit Diagrams

    Page 65...
  • Page 66 Page 66...
  • Page 67 Page 67...
  • Page 68 SEQUENCE OF OPERATION LGA, LGC, LCA, LCC248/300/360 G J M Y NOTE − Steps 12, 17 and 27, beggining with 3 compressor 360H" per- tain only to LGA/LCA360H units equipped with 3 compressors.. Power: 1− Line voltage from TB2, unit disconnect S48, or other factory or field 14−...
  • Page 69: Gas Heat

    GAS HEAT FOR LGA/LGC248/300/360 13 10 Page 69...
  • Page 70 SEQUENCE OF OPERATION FIRST STAGE HEAT: SECOND STAGE HEAT: 1 − Heating demand initiates at W1 in thermostat. 8 − With first stage heat operating, an additional 2 − 24VAC is routed through TB35 to the main con- heating demand initiates W2 in the thermostat. trol module A55.
  • Page 71 A7 diagram EHA−30, 45, 60, 90, 120 − Y Page 71...
  • Page 72: Electric Heat

    SEQUENCE OF OPERATION A7 DIAGRAM − EHA−30, 45, 60, 90, 120 − Y A6 DIAGRAM − EHA−30, 45, 60, 90, 120 − G, J Diagrams A7 and A6 are the EHA electric heat sec- 6 − N.O. contacts K17-1 close allowing the first set of ele- tions used in the LHA and LCA units.
  • Page 73 A6 diagram EHA−30, 45, 60, 90, 120 − G, J Page 73...
  • Page 74 ELECTRONIC OR ELECTROMECHANICAL THERMOSTAT SEQUENCE OF OPERATION POWER: 1 − Terminal strip TB34 energizes the thermostat components with 24VAC via TB1. OPERATION: 2 − The main control module A55 proves the optional N.O. filter switch S27(indicates dirty filter when closed), optional N.O. air flow switch S52(indicates no air [i.e.
  • Page 75: Economizer

    L" SERIES ECONOMIZER SEQUENCE OF OPERATION POWER: 1 − Terminal strip TB34 energizes the economizer components with 24VAC. OPERATION: 2 − The main control module A55 along with outdoor enthalpy sensor A7 and indoor enthalpy sensor A62 (if differential enthalpy is used) communicates to the economizer control module A56 when to power the damper motor B7.
  • Page 76 NOTES Page 76...