Bms Address Tables; Modbus, Trend, Bacnet & Carel - Lennox BAC020SNM Installation, Operating And Maintenance

Table of Contents

Advertisement

CLIMATIC 50 – ROOFTOP – VERSION 23
BMS ADRESS TABLES
ModBus, Trend, BACnet & Carel
Logical
@ (hexa) @ (deci)
01H
1
R/W L [On / Off] Unit
02H
2
R/W L [Reset] Discharges the safety measures of the unit
03H
3
R/W L
04H
4
R/W L
05H
5
R/W L
06H
6
R/W L
07H
7
R/W L
08H
8
R/W L
09H
9
R/W L [Enable] Run eco: [On] the Economiser is running, [Off] the Economiser if stopped.
0AH
10
R/W L
0BH
11
R/W L [Enable] [OFF] Force the unloading of compressors in cooling mode.
0CH
12
R/W L [Enable] [OFF] Force the unloading of compressors in heating mode.
0DH
13
R/W L [Enable] [OFF] Force the unloading of heating module (electric, gas or heat water coil)
0EH
14
R/W L [Enable] [OFF] Force the unloading of humidity control.
0FH
15
R/W L
10H
16
R/W L [Clock] [OFF] read hour & minute [ON] write hour & minute
11H
17
R/W L [Dry contact] Digital Output, Free 1, BM50-J17-NO12
12H
18
R/W L [Dry contact] Digital Output, Free 2, BE50-J5-NO1
13H
19
R/W L [Dry contact] Digital Output, Free 3, BE50-J6-NO2
14H
20
R/W L [Dry contact] Digital Output, Free 4, BE50-J7-NO3
15H
21
R/W L [Dry contact] Digital Output, Free 5, BE50-J8-NO4
16H
22
R/W L not used
17H
23
R/W L not used
18H
24
R/W L not used
19H
25
R/W L not used
1AH
26
R/W L not used
1BH
27
R/W L not used
1CH
28
R/W L not used
1DH
29
R/W L not used
BALTIC R410A-IOM-0708-E
[Enable] Stopping and running of the Fan Blower.[Off] the blower is stopped, [On] the
blower is running.
[Enable] Stopping and running of the fan in the "Control Dead Zone". [Off] the blower
is stopped, [On] the blower is running.
[BMS] Activation of the Unoccupied mode [Off] Occupied mode - [On] Unoccupied
mode
[Room regulation] Choices of the priority of regulation in Heating - [Off] Heat Pump
then Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat
Pump
[F-Air Reheat] Activate reheating of the fresh air in the dead zone to maintain supply
temperature.
[F-Air Reheat] Choices of the priority of regulation in Heating - [Off] Heat Pump then
Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
[Enable] Run CO2 Sensor: [On] Switch-on the CO2 control on a Zone, [Off] Stop the
CO2 control on a zone.
[Unloaded] Force the stop of half of the compressors moving has the moment of the
activation of this point.
DS50
3111
3112
3351
(BMS)
3352
(BMS)
3935
3324
(BMS)
3331
(BMS)
3332
(BMS)
3353
(BMS)
3354
(BMS)
3355
(BMS)
3356
(BMS)
3357
(BMS)
3358
(BMS)
3643
...
2141
2142
2143
2144
2145