Remote On/Off Switch; Electrical Junction Box; Electronic Gas Control Valve - Majestic Vermont Castings Chateau DVT38S2 Installation Instructions And Homeowner's Manual

Direct vent decorative gas appliance
Table of Contents

Advertisement

Chateau
Decorative Gas Appliance
Always check for gas leaks with a mild
soap and water solution applied with a
brush no larger than 1" (25mm). Never
apply soap and water solution with a
spray bottle. Do not use an open flame
for leak testing.
The fireplace valve must not be sub-
jected to any test pressures exceeding
1/2 psi. Isolate or disconnect this or any
other gas appliance control from the gas
line when pressure testing.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to
provide a 1/8" test point up stream of the control.
When using copper, use only approved fittings. Al-
ways provide a union when using black iron pipe so
the gas line can be easily disconnected for burner
servicing. A union may not be behind a wall. (Fig. 8)
See the gas specifications for pressure details and
ratings.

Remote ON/OFF Switch

Do not wire the remote ON/OFF wall
switch for this gas appliance into a 120V
power supply.
The unit is equipped with an ON/OFF rocker switch at
the valve box assembly. If a wall switch is desired,
follow these instructions.
1. The valve box is equipped with two knockouts at the
top right and left corners. The right knockout is
designed to run the wall switch wires to the valve.
Use Romex connectors when running wires through
the valve box where the knockouts are located.
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box.
3. Connect the other end of the wire to the gas control
valve. (Fig. 9)
Remote ON/OFF
Switch
FP1366
Fig. 9 Remote switch wiring diagram for R models.
8
Gas Control Valve
Electrical Junction Box (E Units Only)
The fireplace, when installed, must be
electrically connected and grounded in
accordance with local codes or, in the
absence of local codes, with the current
CSA C22.1 Canadian Electrical Code or
the national electrical code ANSI/NFPA
No. 70 in the USA.
It is strongly suggested that the wiring of
the Electrical Junction Box be carried
out by a licensed electrician. The box
should be near the valve box assembly
to plug the cord into.
Ensure the power to the supply line has
been disconnected before commencing
this procedure.

Electronic Gas Control Valve

This appliance may be fitted with a Honeywell ignition
module. The unit is shipped from the manufacturer with
an ON/OFF switch. The ON/OFF switch is located in
the valve box assembly. If desired a wall switch may
be used.
Installation of the remote ON/OFF switch on electronic
ignition units:
1. The valve box is equipped with two knockouts at the
top right and left corners. The right knockout is
designed to run the wall switch wires to the valve.
The left knockout is designed for wiring the elec-
tronic unit (E model) to 120v with proper grounding.
Use Romex connectors when running wires through
the valve box where the knockouts are located.
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box. (Fig. 10)
3. Connect the White wire from the wall switch to the
Black wire from the transformer, using an approved
wire nut or terminal. Connect the Black wire from
the wall switch to the Black wire running from the #6
position of the ignition module, also using an ap-
proved wire nut or terminal.