Warning:
To install fuel storage tanks the
following checks must be
followed:
1. Location, dimension and safety of the area
where it is installed.
2. The local must be flat, preferently far from
houses, animal shelters, electric installations,
places where there are welding equipments,
boilers, or others that may generate sparks,
blames or excessive heat.
3. Tank must be cylindrical, made of steel plates
electrically welded. Internally, the surface of
the tank and all fuel piping must be clean and
free of any impurities which can contaminate
fuel, it cannot be zinced, because fuel
chemically reacts with zinc, producing a
viscous substance that obstruct filters and
damage fuel injection system functioning.
4. Externally, fuel tank and all components of its
piping must be painted with anti-corrosive paint.
5. Tank must have a ventilation system with inlet
protected with metallic mesh. It is also
possible to install an air filter.
6. Outlet fuel piping must have, after register,
filtering and sedimentation system.
7. If it is necessary to install an electric net to
power pump, that equipment must be
special, armored type.
8. If it is necessary to install a hydraulic pump
for fuel manipulation, this must be protected,
when not in use, from direct contact with fuel,
by a retention valve and register.
9. Hydraulic pump and control panels must be
assembled on bases of concrete.
10. Tank must have a storage register of
sedimented water and impurities.
11. Tank must be installed on appropriated
supports, so that its frontal part, where it is
fuel outlet, stays higher than rear where it is
located drainage register.
INTERNATIONAL ENGINES
8120081 - 05/02 - Service Manual
Additional Instructions