A typical maximum of 40 meters is permitted for sensor runs with unshielded cable. If 
longer distances are required a larger diameter (0.3mm) shielded cable should be used. 
 
When used in Start / Stop commercial programmable mode 
(SW6=on SW8=off), the afterhours run timer can be toggled 
on or off as required with a momentary press button on the 
remote sensor.  See figure 17. 
 
As  the  SMT‐770  "Auto  detects"  sensors  connected  to  the 
"TT" terminals, temperature sensors can also be switched on 
and off as required by placing a switch in the sensor wiring 
Figure 16
to open circuit the sensor loop.  See figure 16. 
Advanced Functions 
 
ModBus Communications 
The  SMT‐770  has  integrated  ModBus  communications  capabilities  where,  using  a 
remote PC or building Direct Digital Control (DDC) system may view or adjust many of 
the SMT‐770 functions remotely.  
 
It is not the scope of this manual to provide detail on the communication capability of 
the  SMT‐770.  Detailed  ModBus  communications  detail  is  available  for  download  from 
the download page at www.thermostat.com.au 