Commissioning 
 
As with any thermostat, commissioning ensures that the thermostat and the equipment 
connected  to  it  are  operating  correctly  and  as  expected.  Although  the  SMT‐770  is  a 
multifunctional thermostat, commissioning is quite a  simple process. Follow the steps 
detailed  below  and  use  the  troubleshooting  guide  on  page  44  if  you  encounter  a 
problem.  
 
When the thermostat is fitted to the base plate and when 24VAC power is first applied, 
the LCD should briefly show all available segments (a LCD function test) then display the 
software version number before showing the time and operating mode etc. 
 
The SMT‐770 is fitted with a number of safety and energy saving time delays. If desired, 
these  can  be  disabled  for  commissioning  purposes  by  entering  the 
installer  mode  and  setting  the  CD=00  value  to  read  CD=01.  After  exiting 
the  installer  menu  you  will  note  a  "Spanner"  icon  flashing  on  the  LCD  to  remind  you 
that  commissioning  mode  is  Active.  After  commissioning  has  been  completed  it  is 
important  to  disable  commissioning  mode  by  entering  the  installer  menu  once  again 
and setting the CD=01 value back to CD=00.  
 
Note‐  when  in  commissioning  mode  ALL  time  delays  are  either  OFF  or 
reduced to a extremely low value, it is therefore normal to potentially call 
rd
for 3
 stage heating almost instantly 0.5deg below the heating set point.  