Anti‐Freeze Function; Occupied Mode Heat Set; Occupied Mode Cool Set; Stage 1 Span - Smart temp SMT?770 Installer Manual

Chameleon multifunction thermostat
Hide thumbs Also See for SMT?770:
Table of Contents

Advertisement

AF = 0 
Anti‐Freeze Function
AF = 0 ‐ Antifreeze function off. 
AF = 1 ‐ Room temperature will not be permitted to fall below 5c (41F). 
oH = Off  Occupied Mode Heat Set  (see page 11 for more information).
Only operates if TT=OC. 
This  is  the  heating  temperature  that  will  be  used  in  "Occupied  mode"  and  will 
temporarily  replace  the  user  heat  set  point  while  the  TT  terminals  are  shorted 
together. 
Adjustable range 0‐35c (32 – 95f) 
oC = OFf   Occupied Mode Cool Set  (see page 11 for more information).
Only operates if TT=OC. 
This  is  the  cooling  temperature  that  will  be  used  in  "Occupied  mode"  and  will 
temporarily  replace  the  user  cool  set  point  while  the  TT  terminals  are  shorted 
together.  
Adjustable range 5‐37c (41 – 98f) 
SP = 2  
Stage 1 Span (See page 33 for an overview of this control function) 
Hysteresis for Stage 1.  
(difference between heating and cooling turning on and off) 
Sp = 1 
0.5c 
SP = 2 
1.0c 
Sp = 3 
1.5c 
 
 
 
27 | P a g e
 